4. Operation
Parallel ID: Parallel operation ID. The ID must be modified after setting Work Mode to Parallel Mode. The value can be
1 to 4. Default value is 1.
Parallel for Capacity UPS Units: Parallel cabinet number. The total parallel cabinet number must be modified after
setting Work Mode to Parallel Mode. The value can be 2 to 4. The default value is 2.
Parallel for Redundancy UPS Units: Parallel redundancy cabinet number. The redundancy cabinet number can be
modified after setting Work Mode to Parallel Mode. The value can be 0 to 3. The default value is 0.
Figure 4-26: Parallel Setup Configurations
3. Click the Output Setup icon and select the configuration to be changed/saved. Click the Back icon to return to the
previous window, or click the Home Page icon to jump to the main page.
Output Freq: Output frequency. The value can be 50 Hz or 60 Hz.
Output Volt Level: Output voltage level. The value can be 120 or 127.
Output INV Volt Regulation: Inverter voltage regulated. The value can be between -5% to +5% in 1% increments.
The default value is 0%.
Figure 4-27: Output Setup
51