P-3600 AR G OWNER'S MANUAL
Selecting The SUPPLY Cable
For nominal 120 VAC operation, 3 conductor cable of at least 10 AWG (.101"/2.56mm diameter) should be used, depending on
distance from the power source.
For nominal 208-240 VAC operation, 3 conductor cable of at least 14 AWG (.064"/1.62mm diameter) should be used, depending on
distance from the power source.
Rubber-jacketed cable is highly recommended for best flexibility and abrasion resistance. It is permissible to use 4 conductor cable, but
it is not necessary to do so and is not recommended.
Supply Cable Wiring Instructions
Refer to the following diagrams for wiring the twist-lock connector:
(120V NEUTRAL ONLY)
(220-240 ONLY *SEE BELOW)
General Wiring Requirements:
Low Range Voltage (88 to 133VAC, 30A max) is applied between X and W.
High Range Voltage (170 to 265VAC, 15A max) is applied between X and Y.
G is always Equipment Ground.
For 120V Wiring:
Wire hot lead to X (black in North America).
Wire the neutral lead to W (white in North America).
Wire the equipment ground to G (green in North America).
220-240V US Wiring:
Wire hot lead to X (black in North America).
Wire hot lead to Y (red or blue in North America)*.
Wire the equipment ground to G (green in North America).
220-240V Europe Wiring:
Wire hot lead to X (brown, or black with white stripes in Europe).
Wire neutral lead to Y (blue in Europe)*.
Wire the equipment ground to G (green with yellow stripe in Europe).
Source-End Connector On Supply Cable:
The connector used at the source end should be rated at least 250V-15A for high range operation, or 120V-30A for low range
operation. If in doubt, consult a licensed electrician when installing your P-3600 AR G.
OPERATION
Ultra-Low Resistance Magnetic Power Switch/Circuit Breaker:
Furman's Prestige Series 30 amp capacity power switch / circuit breaker is specifically designed to stand up to the enormous high in-
rush current demands of many power amplifiers. Additionally, Furman magnetic circuit breakers are not sensitive to temperature, nor
do they raise the AC impedance as do many less costly thermal breakers. If the 30 amp maximum RMS current capacity of the P-3600
AR G is exceeded, the spring tensioned switch will immediately reset to the "Off" position. Once the problem is corrected or once the
RMS current load is adjusted to no longer exceed 30 amps / 3600 watts (typically by unplugging one component), a person can switch
the unit back to the "On" position. The P-3600 AR G will then resume operation as normal.
Total Current Capacity (maximum and minimum load):
The P-3600 AR G can handle loads totaling up to 3600 watts as long as the input voltage is equal to or above the unit's low range or