Installation Guide
Connecting more
Danfoss Icon™
Master Controllers in
a system
Test procedures for
multiple Danfoss
Icon™ Controllers in a
system
VIMCG20F / 088N3678
Danfoss Icon™ Master Controller 24 V
If wired system
Connect up to three Danfoss Icon™ Master
Controller 24V to each other with a 4-wire twisted
pairs cable and the supplied connector.
4 (2 x twisted pairs)
Cable pin out
1
2
3
1. GND
2. COM A
3. COM B
NET TEST on System Slave
1. Install all thermostats and actuators as de-
scribed in the Quick Guide D2 to D6.
2. Perform Network test. Press
and press
to choose NET TEST. Confirm
with OK (Quick Guide E7 and E8).
3. After completing the TEST press
RUN mode and press OK (Quick Guide E9).
APP TEST on System Master
1. Perform application test. Press
TEST and press
to choose APP TEST. Con-
firm with OK (Quick Guide E7 and E8).
2. After completing the TEST press
RUN mode and press OK (Quick Guide E9).
Note! If an Expansion Module is added to the system,
it must be installed on the Master Controller.
If wireless system
Wireless connection of up to three Danfoss Icon™
Master Controllers 24V requires a Radio Module
with each Master / Slave.
Connecting procedure for multiple Danfoss
Icon™ Controllers in a system
On System Master
Max. 3 x Master
1. Install all thermostats and thermal actuators as
Controllers in one
described in the Quick Guide D2 to D6.
system.
2. Perform network test. Press
and press
witk OK (Quick Guide E7 and E8).
Pairing Master and Slave
Note! Slave Controllers must be assigned as System
Slaves before assigning outputs and thermostats to
them.
1. On the selected system master, press
select INSTALL mode.
2. On the system slave, press and hold
1.5 sec. The display now toggles between SLA
TYPA and SLA TYPB.
3. Press
types and confirm with OK. See "Slave type
definition" on the next page.
4. Repeat step 4 and 5 to assign a 2
Controller to the system (max. two slaves are
permitted).
Changing Slave type
1.
On Danfoss Icon™ Slave Controller press and
hold
to select TEST
between SLA TYPA and SLA TYPB.
2. Press
types and confirm with OK. See "Slave type
to select
definition" for more information.
LINK test on Slave (between Master and Slave)
Press
for 1.5 sec. The display shows inclu-
to select
sion pattern while making the LINK test. When
done, the display shows the number of packages
recieved in percentage.
to select
to select TEST
to choose NET TEST. Confirm
for
to choose between the two slave
nd
Slave
for 1.5 sec. The display now toggles
to choose between the two slave
© Danfoss | FHEC| 2017.06 | 9
GB
to