Honeywell ML7999C Notice Technique

Honeywell ML7999C Notice Technique

Actionneur universel à repositionnement parallèle

Publicité

Les langues disponibles

Les langues disponibles

Liens rapides

ML7999C Universal
Parallel-Positioning Actuator
APPLICATION
ML7999C Universal Parallel-Positioning Actuator
provides 100 lb-in. torque, pulse-width-modulating
(PWM) control of combustion air dampers, butterfly gas
valves, oil modulation valves, and flue gas recirculation
systems. The actuator includes a precision feedback
potentiometer and integral power supply capable of direct
line voltage connection. The ML7999C Actuator is part of
the ControLinks™ Control System, and must be used with
the R7999C ControLinks™ Controller.
Application .....................................................................................
Features ..........................................................................................
Specifications ...............................................................................
Ordering Information ................................................................
Installation .....................................................................................
Wiring ...............................................................................................
Operation .......................................................................................
Checkout And Troubleshooting .............................................
FEATURES
• Universal power supply input.
• Password protected with an eight-digit hexadecimal
identification signal.
• 100 lb-in. (11.3 Nm) torque.
• Includes integral position feedback potentiometer.
• Separate wiring compartment between line voltage
power wiring and low voltage control.
• Direct coupling shaft interface mounting.
• Couples directly to a 1/2 in. (13 mm) shaft with no
additional parts required.
• Couples directly to 5/16 in. (8 mm) and 3/8 in. (9
mm) shafts using available self-centering shaft
reduction accessories.
• Shaft coupler assembly available for shafts larger
than 1/2 in.
• Bracket Accessory Kit available for mounting to
Honeywell V51 Butterfly Gas Valves.
• Visual indication of actuator position.
• NEMA 3 rating with optional weatherproof kit.
• UL, FM, CSA approved.
SPECIFICATIONS
Model:
ML7999C Universal Parallel-Positioning Actuator.
Medium torque electronic actuator with a precision
feedback potentiometer and integral power supply
capable of direct line voltage connection.
Dimensions: See Fig. 1.
Electrical Ratings:
Power Input: 100 to 240 Vac +10% -15%, 50/60 Hz.
Maximum Power Consumption: 15 VA.
IMPORTANT
Device must be hardwired.
Temperature Range:
Contents
Ambient: -40°F to +140°F (-40°C to +60°C).
Storage: -40°F to +150°F (-40°C to +66°C).
1
1
Humidity Range (at 95°F [35°C]): 5 to 95 percent relative
1
humidity, noncondensing.
2
3
4
5
8
PRODUCT DATA
32-00079EF-01

Publicité

Table des Matières
loading

Sommaire des Matières pour Honeywell ML7999C

  • Page 1: Table Des Matières

    ML7999C Universal Parallel-Positioning Actuator. potentiometer and integral power supply capable of direct Medium torque electronic actuator with a precision line voltage connection. The ML7999C Actuator is part of feedback potentiometer and integral power supply the ControLinks™ Control System, and must be used with capable of direct line voltage connection.
  • Page 2: Ordering Information

    TRADELINE® Catalog or price sheets for complete ordering number. If you have additional questions, need further information, or would like to comment on our products or services, please write or phone: 1. Your local Honeywell Environmental and Combustion Controls Sales Office (check white pages of your phone directory).
  • Page 3: Installation

    Specifications section. Fig. 2. V5197A Firing Rate Gas Valve, with Mounting ML7999C Actuator mounting bracket (included) and ML7999C Actuator (not supplied), dimensions in in. (mm). The actuator mounts on a 1/2 in. round or square shaft. For...
  • Page 4: Wiring

    1. Attach the mounting bracket for the ML7999C Actu- ator (supplied with the V5197 Valve) in the position IMPORTANT...
  • Page 5: Operation

    M16470 CCW. To use them, the only required wiring connections are L1, L2, and GND. However, after Fig. 5. Opening ML7999C low-voltage wiring the device is installed and wired to the R7999, do compartment. not use these buttons for anything but troubleshooting.
  • Page 6 CW/CCW buttons to find the mechanical fixed IF the system is being commissioned, perform the stop of the actuator. The air/fuel/fgr is not connected following to set the ML7999C and linkage/damper of the at this time. air/fuel/fgr. MOVE ACTUATOR 5 DEGREES MOVE ACTUATOR 5 OFF MECHANICAL FIXED STOP.
  • Page 7 ML7999C UNIVERSAL PARALLEL-POSITIONING ACTUATOR 6. Move the actuator/linkage/damper two to five 8. Move the actuator five (5) degrees off the mechanical degrees off the linkage/damper mechanical closed open stop. See Fig.12. fixed stop. Lock actuator closed position. See Fig. 10.
  • Page 8: Checkout And Troubleshooting

    ML7999C UNIVERSAL PARALLEL-POSITIONING ACTUATOR CHECKOUT AND c. Press the button labeled CCW. The actuator should drive the device counterclockwise. TROUBLESHOOTING 4. If the actuator operates properly, check the control- ler for proper output signals. 5. If the actuator does not drive, remove power, discon-...
  • Page 9: Caractéristiques

    • Homologation à la norme NEMA 3 avec la trousse de L’actionneur universel à repositionnement parallèle protection optionnelle contre les intempéries. ML7999C fournit un couple de 100 lb-po et comporte une • Approuvé UL, FM et CSA. commande à modulation d’impulsions en durée (PWM) des registres d’air de combustion, en plus d’être muni de...
  • Page 10: Pour Commander

    écrit ou par téléphone : 1. Au bureau des ventes de la Régulation d'ambiance et de combustion Honeywell de votre localité (consulter les pages blanches de l'annuaire téléphonique).
  • Page 11: Emplacement

    (153) Peut causer des blessures graves ou le décès. Débranchez l’alimentation avant de commencer l’installation. M16466 Fig. 1. Dimensions en po (mm) du ML7999C. Emplacement MISE EN GARDE Risque d’endommagement de l’actionneur. 7-1/8 Les vapeurs destructrices et les vapeurs d’acides (181) peuvent endommager les pièces métalliques de...
  • Page 12: Câblage

    électriques locaux. régulateur V5197 de façon à ce que la partie L’actionneur ML7999C est conçu pour être utilisé avec une rectangulaire de la tige se trouve à l’intérieur de alimentation de classe 2 à basse tension. La tension et la l’entraînement.
  • Page 13: Procédures De Câblage

    L’actionneur universel à repositionnement parallèle 2. Tirez les crochets de verrouillage vers l’arrière tout en ML7999C est conçu pour actionner des registres d’air de ouvrant le compartiment basse tension. Voir la Fig. 5. combustion, des vannes papillon à gaz, des vannes de 3.
  • Page 14 DE L’ACTIONNEUR. DE L’ACTIONNEUR. Butées fixes d’ouverture/de fermeture mécanique de l’actionneur (ML7999C). Déplacez l’actionneur de 5 degrés par rapport à la butée de fermeture mécanique fixe. Vérifiez que les registres d’air, de carburant et de recirculation des gaz de combustion ont été ajustés par rapport à leurs positions de fermeture mécanique fixe.
  • Page 15 ACTIONNEUR UNIVERSEL À REPOSITIONNEMENT PARALLÈLE ML7999C 6. Déplacez la tringlerie et le registre de l’actionneur de 2 à 5 degrés par rapport à la butée de fermeture mécanique de la tringlerie et du registre. Verrouillez la position fermée de l’actionneur. Voir la Fig. 10.
  • Page 16: Vérification Et Dépannage

    ACTIONNEUR UNIVERSEL À REPOSITIONNEMENT PARALLÈLE ML7999C VÉRIFICATION ET DÉPANNAGE Vérification Consultez la documentation du contrôleur R7999C et le formulaire 32-00081EF pour la vérification du système. Dépannage Si l’actionneur ne fonctionne pas correctement lors de la vérification, effectuez les étapes de dépannage suivantes.

Table des Matières