BEFORE INSTALLATION
The MP909D Pneumatic Damper Operator can be mounted in
any position, externally or internally.
Pneumatic air connection is sized for 5/32-inch (4 mm) or
1/4-inch (6 mm) O.D. plastic tubing.
Installation requires no special tools.
INSTALLATION
Ball Joint Type Linkage
1. Refer to Fig. 1 for dimensions.
2. Select mounting location.
3. Using the mounting bracket as a template, mark two
mounting holes.
4. Drill or punch two mounting holes and secure mounting
bracket with screws provided.
5. Install operator on mounting bracket with two No. 8 x 1/2
self-tapping screws (see Fig. 2).
6. Screw locknut and motor shaft balljoint onto operator
shaft (see Fig. 3).
7. Tighten locknut against motor shaft balljoint.
8. Install crankarm balljoint on crankarm.
9. Secure crankarm to damper drive axle.
10. Cut 5/16-inch pushrod to length.
11. Slide pushrod onto crankarm balljoint and motor shaft
balljoint.
12. Tighten balljoint setscrews.
13. Push plastic tubing from controller branch line onto
operator inlet port.
NOTE: NOTE:After tubing is connected, do not
attempt to remove it. If it must be
disconnected, cut the tubing and reconnect
with a barb coupling.
® U.S. Registered Trademark
Copyright © 2000 Honeywell Inc. • All Rights Reserved
Pneumatic Damper Operator
2-3/8
(61)
1/2 (13)
Fig. 1. MP909D approximate dimensions in in. (mm).
OPERATOR SHAFT
LOCKNUT
MOTOR
SHAFT
BALLJOINT
5/16 in.
PUSHROD
SETSCREW
INSTALLATION INSTRUCTIONS
1/4 DIA (6)
5-11/16 (145)
OPERATOR
OPERATOR
SHAFT
SELF-TAPPING
SCREW
Fig. 2. Operator mounting.
CRANKARM
BALLJOINT
DAMPER
AXLE
CRANKARM
Fig. 3. Ball joint linkage.
MP909D
3/8-16 UNC-2A
13/16 (20) LONG
MIN.
OR
1-1/16
1-3/16
(27)
(46)
C484-2
MOUNTING
BRACKET
M16439
INLET
PORT
MOUNTING
BRACKET
M16438
95- 7175EF

Publicité

loading

Sommaire des Matières pour Honeywell MP909D

  • Page 1 INSTALLATION INSTRUCTIONS BEFORE INSTALLATION 3/8-16 UNC-2A 1/4 DIA (6) 13/16 (20) LONG MIN. The MP909D Pneumatic Damper Operator can be mounted in any position, externally or internally. 2-3/8 (61) Pneumatic air connection is sized for 5/32-inch (4 mm) or 5-11/16 (145) 1-1/16 1/4-inch (6 mm) O.D.
  • Page 2 Attach linkage to clevis (see Fig. 4 and 5). When used to operate a small outside air damper on a fan coil unit, the MP909D is controlled by an electric/pneumatic relay. When the fan starts, the normally closed damper opens; when TYPICALLY PROVIDED BY USER the fan stops, the damper closes.
  • Page 3 3/8-16 UNC-2A 20 (0,79) 6 (0,25) DIAM. DE LONG MIN. L'actionneur de registre pneumatique MP909D peut être installé dans toutes les positions, de façon externe ou interne. (2,4) Le raccord d'air pneumatique convient à un tuyau de plastique dont le diamètre extérieur est de 4 mm (5/32 po) ou...
  • Page 4 MP909D. By using this Honeywell literature, you agree that Honeywell will have no liability for any damages arising out of your use or modification to, the literature. You will defend and indemnify Honeywell, its affiliates and subsidiaries, from and against any liability, cost, or damages, including attorneys’...