4.6.8
Adapting the unit to the mains voltage
Fig. 20: Adapting the mains voltage
1
Mating plug
2
Cable
Units with a mains voltage of 400/460 V can be connected optionally to another mains voltage.
The adaptation is made by selecting the appropriate terminal on the mains plug X50.
Mains voltage
400 V, 50 Hz
460 V, 60 Hz
Tab. 14: Adapting the mains voltage
Prerequisite
DANGER – Danger to life due to electric shock. Make sure that the unit is voltage-free.
All general requirements for safe and reliable operation are fulfilled.
Procedure
1.
The mains voltage is now adapted.
Operating Manual | Attachment and Installation Cooling Units | Standard Controller (SC) – 400 V, 2~ | 086100115
Terminal at X50
L1 – 400 V
L1 – 460 V
Select the terminal L1 on the mating plug according to the mains voltage (400/460 V)
3
Control fuse F2
4
Control fuse F3
45/68