ENG
4.5.3
Assembly of the DTI cooling unit (Installation)
4.5.3.1
Making cut-outs for DTI cooling unit
Fig. 12: External view switch cabinet, assembly cut-outs
1
Air inlet
2
Air outlet
Prerequisites
DANGER – Danger to life due to electric shock. Make sure that the unit is voltage-free.
•
All general requirements are met, see "General", Page 30.
Required tools and materials
•
Saw
•
Switch cabinet mill if necessary
•
Protective covers
Procedure
1.
Ensure that the switch cabinet has a protective cover to protect against chips.
Provide switch cabinet with cut-outs. For prescribed dimensions, see Fig. 12.
2.
3.
The four cut-out corners can be made rectangular or with a max. radius of 4 mm.
4.
Deburr the cutting edge.
5.
Remove chips and assembly waste from the switch cabinet.
The cut-outs and holes are made and the cooling unit can be assembled.
Operating Manual | Attachment and Installation Cooling Units | Standard Controller (SC) – 400 V, 2~ | 086100115
3
Device contour
4
Assembly cut-out
G00009
33/68