2004-09-17
3-c Mounting for best EMC behaviour
These sensors radiate almost no electromagnetic
radiation but under adverse conditions can be susceptible
to the effects of external radiation. The body of the
sensor is not itself very susceptible but the voltages
induced in long exposed leads attached to the connector
can cause problems in the sensor.
In many applications the sensors will be fitted inside
metal cabinets and have short leads. In such applications
no further precautions will normally be needed.
In applications that require that the sensor be used with
exposed long leads, a screened cable should be used with
the screening earthed at both ends (See Fig 5).
I p
ABB Entrelec
1SBC146002M1701
1 2 3 4
Screened Cable
– Control Division
Version 1.0
3-c Montage pour meilleur comportement CEM
Ces
capteurs
n'émettent
radiations
électromagnétiques
sensibles aux effets de radiations externes. Le corps du
capteur n'est pas lui-même très sensible mais les
tensions induites dans les longs câbles reliés au
connecteur peuvent poser des problèmes dans le capteur.
Dans de nombreuses applications les capteurs seront
montés dans des armoires métalliques et auront des fils
courts. Dans de telles applications, aucunes précautions
particulières ne sont normalement nécessaires.
Dans les applications qui imposent que le capteur soit
utilisé avec de longs câbles exposés, un câble blindé
devrait être utilisé, avec le blindage relié à la masse aux
deux extrémités (Voir Fig. 5)
Measuring Device
-Va
+Va
Fig. 5