Maintenance
Troubleshooting
Servicing
The Altivar 11 does not require any
preventative maintenance. It is
nevertheless advisable to carry out the
following operations regularly :
Check the condition and tightness of
connections.
Check that the temperature around
the unit remains at an acceptable
level and that the ventilation is
effective (average service life of fans
: 3 to 5 years depending on
operating conditions).
Remove any dust from the speed
controller.
Faults
OCF
Overcurrent
SCF
motor short-circuit
InF
Internal fault
CFF
Configuration fault
SOF
overspeed
CrF
capacitor charging circuit
OHF
Speed drive controller
overload
OLF
Motor overload
OSF
Overvoltage in steady state
or during acceleration
ObF
Overvoltage during
deceleration
PHF
Phase failure
USF
Undervoltage
Causes
Ramp too short
Inertia or load too high
Mechanical blocking
Short-circuit or earthing at the speed drive
controller output
Internal fault
The current configuration is
inconsistent
instability or
driving load too high
load relay control fault or damaged load resistor Replace the drive.
2
I
t too high or speed controller temperature too
high
2
Tripped by I
t motor being too high
Line voltage too high
Disturbed line supply
Braking too sudden or driving load
Speed drive controller incorrectly supplied or a
fuse blown
Transient phase fault
Unbalanced load
This protection only operates with the drive on
load.
Line supply too low
Transient voltage dip
Damaged load resistor
06/2005 - Art. Nr. 13 019 652A
Corrective actions
Check the settings.
Check the motor / speed controller / load sizing.
Check the state of the mechanism.
Check the cables connecting the speed controller to the
motor, and the insulation of the motor.
Check the environment (electromagnetic compatibility).
Check that the "local control" option has not been connected
or disconnected with the controller powered up.
Send the speed controller to be checked / repaired.
Return to factory settings or call up the backup configuration,
if it is valid. See parameter FCS in the FUn menu.
Check the motor, gain and stability parameters.
Add a braking resistor and module.
Check the size of the motor/drive/load.
Check the motor load, the speed controller ventilation and the
environment. Wait for the controller to cool before restarting.
Check the setting of the motor thermal protection, check the
motor load. Wait for the controller to cool before restarting.
Check the line voltage.
Increase the deceleration time.
Install a braking resistor if necessary.
Activate the brA function if it is compatible with the
application.
Check the power connection and the fuses.
Reset
Disable the fault by setting IPL = nO (FUn menu)
Check the voltage and the voltage parameter.
Reset.
Send the speed controller to be checked / repaired.
15