5. Electrical work
1-3/16
1-3/16
(30)
1-37/64 (46)
Fig. 5-5
(2)
(3)
Fig. 5-6
Fig. 5-7
5.8. Electrical characteristics
Model
PMFY-P06NBMU-E
PMFY-P08,12NBMU-E
60Hz
PMFY-P15NBMU-E
10
(30)
Remote controller profile
Required clearances surrounding
the remote controller
Installation pitch
B
-
. 1
B
-
. 2
AB
TB6
Power supply
Hz
Volts
208 / 230V
5.7. Remote controller
in. (mm)
For wired remote controller
1) Installing procedures (Fig. 5-5)
(1) Select an installing position for the remote controller.
The temperature sensors are located on both remote controller and indoor unit.
► Procure the following parts locally:
2 piece switch box
Thin copper conduit tube
Lock nuts and bushings
(2) Seal the service entrance for the remote controller cord with putty to prevent
possible invasion of dew drops, water, cockroaches or worms. (Fig. 5-6)
For installation in the switch box:
A
For direct installation on the wall select one of the following:
B
• Prepare a hole through the wall to pass the remote controller cord (in order to run
the remote controller cord from the back), then seal the hole with putty.
• Run the remote controller cord through the cut-out upper case, then seal the
cutout notch with putty similarly as above.
B-1. To lead the remote controller cord from the back of the controller:
B-2. To run the remote controller cord through the upper portion:
(3) For direct installation on the wall
Wall
C
Conduit
D
Lock nut
E
Bushing
F
2) Connecting procedures (Fig. 5-7)
Connect the remote controller cord to the terminal block.
1
To TB5 on the indoor unit
A
TB6 (No polarity)
B
3) Temperature display setting
The initial temperature display setting is °C. Please change the setting to °F. Refer
to "Function selection of remote controller (Section 8)" in the operation manual for
the indoor unit.
4) 2 remote controller setting
If 2 remote controllers are connected, set one to "Main" and the other to "Sub".
For setting procedures, refer to "Function selection of remote controller" in the
operation manual for the indoor unit.
Symbols: MCA: Max. Circuit Amps (= 1.25×FLA)
IFM: Indoor Fan Motor
Voltage range
MCA (A)
0.25 / 0.25
198 to 253V
0.26 / 0.26
0.33 / 0.33
Switch box
G
Remote controller cord
H
Seal with putty
I
Wood screw
J
FLA: Full Load Amps
Output: Fan motor rated output
IFM
Output (kW)
FLA (A)
0.028 / 0.028
0.20 / 0.20
0.028 / 0.028
0.21 / 0.21
0.028 / 0.028
0.26 / 0.26