Test ADC settings:
To test the desired ADC settings, use the command:
TEST ADC #1513
To use the analogue input for the temperature sensor, use the command:
SET ADCMODE TEMP #1513
Then the temperature sensor (e.g. Conrad item no. 198896) is evaluated at the analogue input
accordingly.
To switch off the temperature measurement at the analogue input (IN1) and to reset it for
voltage measurement send the following command:
SET ADCMODE VOLT #1513
To test the desired settings, use the command:
TEST ADCMODE #1513
ADC in the Temperature Mode
The sensor´s temperature range is between -40°C and +125°C. If no sensor is connected, the
output will be "-40°C". You can set a MAX and a MIN temperature value for the temperature
sensor. When the MIN value is undercut or the MAX value exceeded, an alarm message is sent
to all stored phone numbers and the email.
Do set it, use the following command:
SET TEMPERATURE <Temp1> <Temp2> #1513
Temp1 = upper threshold
Temp2 = lower threshold
The "Temp1" value must be higher than the "Temp2" one!
Example:
SET TEMPERATURE +250 -050 #1513
In case of a temperature of less than -5.0°C or more than +25.0°C at the ADC, the "GX107"
will give an alarm.
The threshold value range can be set between -400 and +1250.
If "Temp1" = "+1250" is set, the upper threshold is deactivated.
If "Temp2" = "-400" is set, the lower threshold is deactivated.