Wiring
Before installation, make sure that
power has been switched off at the
breaker and check that the circuit is
dead with a voltage tester.
The leads consist of four wires:
Wiring for 480VAC, 60Hz, 2 phase
applications (US) involves 4 wires:
1. Black – Phase A Line voltage (Hot)
2. Red – Phase A Load (Switched Hot).
3. Black with White Stripe – Phase B
Line voltage (Hot)
4. Red with White Stripe – Phase B
Load (Switched Hot)
480 VCA, 60 Hz Wiring
B PHASE
(BlACk WitH WHitE StriPES)
A PHASE
(BlACk)
347 VAC, 60 Hz Wiring
NEUtrAl
(BlACk WitH WHitE StriPES)
HOt
(BlACk)
Wiring for 347VAC, 60Hz, single phase
applications (Canada) involves 3 wires:
1. Black – 347Vac Line voltage (Hot)
2. Red – Load (Switched Hot)
3. Black with White Stripe – Neutral
4. The Red with White Stripe wire will
be capped off and not used.
(rEd WitH WHitE StriPES)
lOAd B
(rEd)
lOAd A
NEUtrAl
(rEd WitH WHitE StriPES)
(rEd)
lOAd
- 6 -
Operation
The HBS 300 (347-480V) and HBS
200 (347-480V) operate by turning
lights ON automatically when
occupancy is detected and OFF when
the space is left vacant and the time
delay has elapsed.
Light level function
The light level (Hold OFF) feature
keeps lighting OFF during daylight
hours, regardless of occupancy.
Initial power up
Upon initial power up, the load will
turn ON for up to one minute. If no
motion is detected, the load will
switch OFF. If motion is detected and
the target light level setting is less
than the daylight level, the load will
stay ON for the selected time delay
setting (per DIP switch setting). If the
daylight level at power up is greater
than the target light level setting, the
load will switch OFF regardless of
occupancy.
Surge protection
The surge protection feature will reset
the sensor automatically after: power
surges, power outages, and power
shortages. Surge protection protects
the sensor if it is miswired as well.
If miswired, shut off power, correct
the wiring, and the sensor will then
operate correctly.
- 7 -