6. Settings
6.6 Limit values for gases
EN
N₂-Analyser
The factory settings are the limits for the reusable SF
Recycling Guide or IEC 60480. The limits of the installed sensors can be adjusted
according to customer guidelines.
Lower limit of SF
■
Upper limit of contamination of SF
■
Upper limit of contamination of He: user-defined
■
Upper limit of moisture: -36.0 °C dew point
■
Flow duration: 450 seconds, flow duration = measurement duration
■
28
All manuals and user guides at all-guides.com
: 97 vol. %
6
: user-defined
6
WIKA operating instructions analytic instrument, model GA11
gas according to the Cigré
6