V8043C, D, F & G 5000 SERIES MOTORIZED ZONE VALVES
Auxiliary Switch Rating:
'G' & 'F' Model
- 50 VA pilot duty at 24 Vac.
- 4.4 Amps running at 120 Vac, 60 Hz.
Recommended Wall Thermostats:
Heating Only - T86A, T822D: (T822C for normally open
[N.O.] valves).
Cooling Only, or Heating-Cooling - T87F with Q539.
Thermostat Heater Setting:
For heat anticipation: 0.3 Amps.
Replacement Powerheads:
'C' Model
- P/N 40003916-511
'D' Model
- P/N 40003916-514
'G' Model
- P/N 40003916-512
'F' Model
- P/N 40003916-548
LEADWIRES
A
AUTO
MAN
OPEN
IN
DIMENSION IN INCHES (MM)
MODELS
V8043C,D,G
2-3/8 (60)
V8043F
2-3/8 (60)
SWEAT MODELS
5/8 IN. I.D. (FOR 1/2 IN. COPPER TUBING)
7/8 IN. I.D. (FOR 3/4 IN. COPPER TUBING)
1-1/8 IN. I.D. (FOR 1 IN. COPPER TUBING)
FNPT MODELS
3/4 IN.
95C-10938EF—04
TERMINAL BOARD
CLEARANCE
FOR COVER
REMOVAL
D
1
F
B
AUTO
C
3/8 FLARE
OUT
N
S
M
R
A
B
C
3-3/4 (90)
7/8 (22)
3/4 (19)
3-3/4 (90)
7/8 (22)
3/4 (19)
K
3-1/8 (79)
1-9/16 (40)
3-1/2 (89)
1-3/4 (44)
3-7/8 (98)
1-15/16 (49)
P
3-5/8 (98)
1-13/16 (46)
Fig. 1. Dimensions in inches (mm).
NOTE: The standard valve is not recommended for
steam service. Consult your local Resideo repre-
sentative whenever steam applications are
involved.
Accessories:
Flare-to-Sweat Union Adapters (sold in sets of 2)
3/8 Flare to 1/2 sweat - P/N 272704A
3/8 Flare to 3/4 sweat - P/N 272704B
Service Medium:
Suitable for glycol/water mix up to 50:50 use in closed
hydronic systems. Not for use with oxygenated water,
potable water or steam.
Use this valve in hydronic systems which DO NOT contain
dissolved oxygen in the system water. The dissolved
oxygen, which is found in systems that have a frequent
source of make-up water, causes the rubber plug inside
the valve to deteriorate and eventually fail.
Approvals: CSA C/US Certified.
CONDUIT COVER
FOR V8043F
A
END SWITCH
B
B
MAN
OPEN
C
2
IN
1
CLEARANCE NECESSARY FOR COVER REMOVAL
2
FLAIR-TO-SWEAT UNION ADAPTER
D
E
F
—
5-1/4 (133)
3-7/16 (87)
3-7/8 (98)
5-1/4 (133)
3-7/16 (87)
L
FLARE MODELS
3/8 IN NPT ONLY
FLARE-TO-SWEAT UNION ADAPTER
FOR 1/2 IN. COPPER
U
FOR 3/4 IN. COPPER
2
SWEAT
4-7/8 (124)
G
J
H
L
K
FNPT
OUT
U
P
G
H
J
5/8 (16)
—
—
3/4 (19)
M
N
4-5/8 (117)
2-5/8 (59)
R
S
6-3/16 (157)
3-29/32 (99)
6-7/16 (164)
4-13/16 (106)
M16851