Steam Line Installation Examples
12 (305)
4 (102)
MINIMUM
12 (305)
MINIMUM
RADIUS
HM750
Status
Idle
Filling
Humidifying
Draining
Service
Cylinder
Fault
Power
Drain
Fault Codes In Front Cover
Fig. 9. Steam distributor above humidifier (hose).
Measurements in inches (mm).
INSUFFICIENT
BEND RADIUS
INSUFFICIENT
BEND RADIUS
STEAM LINE
NOT SLOPED
HM750
Status
Idle
Filling
Humidifying
Draining
Service
Cylinder
Fault
Power
Drain
Fault Codes In Front Cover
Fig. 11. Common steam line installation errors.
33-00289EF—02
SUPPORT
BRACKETS
CONNECT
STEAM
HOSE TO
CYLINDER
M37200
NO
CONDENSATE
TRAP AT
VERTICAL
TRANSITION
M37205
12 (305)
MINIMUM
RADIUS
HM750
Status
Idle
Filling
Humidifying
Draining
Service
Cylinder
Fault
Power
Drain
Fault Codes In Front Cover
12 (305)
MINIMUM
HOSE WILL SOFTEN OVER TIME. PROPER SUPPORT IS NECESSARY.
1
Fig. 10. Steam distributor below humidifier with
obstruction (hose). Measurements in inches (mm).
8
1
SUPPORT
BRACKETS
OBSTRUCTION
12
(305)
MINIMUM
4 (102)
MINIMUM
USE FULL SIZE CONDENSATE
TEE AT LOW POINT. SLOPE
LINES UP TO "T" AND
IMMEDIATELY AFTER IT.
TO DRAIN
M37204