HM700AFVALVE
ELECTRODE STEAM HUMIDIFIER
FILL VALVE REPLACEMENT
CAUTION
Before Servicing
1. Disconnect main power source before
accessing internal compartments.
2. The plumbing and electrical compartments
contain high voltage components and wiring.
Access should be limited to licensed HVAC
professionals only.
3. During and following operation of the
humidifier, the steam components in contact
with the steam such as the cylinder, steam
lines, steam distributors, and condensate lines
can become hot and burn if touched.
4. Installations of humidity equipment installed by
unqualified personnel or the use of non-
Honeywell parts and components will void
warranty.
Included in the Box
• Fill Valve
• Tie Wrap
• Clip
• Phillips Head Screws
• Installation Instructions
Tools Needed
• Screwdriver
• Pliers
Step 1
Refer to the humidifier operating manual if necessary.
1. Shut off water supply to the unit.
2. Disconnect power to unit.
3. Locate Fill Valve.
4. If necessary, remove cylinder.
Step 2
Removing old Fill Valve
1. Disconnect the wiring to the solenoid.
2. Using pliers, slide the spring clamp up the hose.
3. Disconnect the hose from the fill valve.
INSTALLATION INSTRUCTIONS
CAUTION
The remaining water located in the hose will
spill out.
Have something on hand to absorb the water.
VALVE HOSE
SPRING CLAMP
Fig. 1. Disconnecting old fill valve.
Step 3
1. On the opposite side of the wall where the valve is
mounted, unscrew the fitting from the fill valve, and
remove screws.
REMOVE
SCREWS
Fig. 2. Removing old fill valve.
WIRE
TERMINALS
M35701
REMOVE
FITTING
M35702
33-00158EFS-01

Publicité

loading

Sommaire des Matières pour Honeywell HM700AFVALVE

  • Page 1 4. Installations of humidity equipment installed by unqualified personnel or the use of non- Honeywell parts and components will void warranty. Included in the Box • Fill Valve •...
  • Page 2 1-800-468-1502 or 1-800-814-9452 Automation and Control Solutions Honeywell International Inc. 1985 Douglas Drive North ® U.S. Registered Trademark Golden Valley, MN 55422 © 2016 Honeywell International Inc. 33-00158EFS—01 M.S. 03-16 customer.honeywell.com Printed in United States...
  • Page 3 4. L'installation d'humidificateurs par un personnel non qualifié et l'utilisation de pièces et de composants non fabriqués par Honeywell COSSES DE BRIDE À RESSORT CÂBLE DU TUYAU DE VANNE annuleront la garantie.
  • Page 4: Installation De La Vanne De Remplissage Neuve

    1-800-468-1502 ou le 1-800-814-9452. Solutions de régulation et d’automatisation Honeywell International Inc. 1985 Douglas Drive North ® Marque de commerce déposée aux États-Unis Golden Valley, MN 55422 © 2016 Honeywell International Inc. 33-00158EFS—01 M.S. 03-16 customer.honeywell.com Imprimé aux États-Unis...
  • Page 5: Artículos Incluidos En La Caja

    4. Las instalaciones del equipo de humidificación Tenga a mano algo para absorber el agua. que no sean realizadas por personal autorizado y el uso de piezas y componentes que no sean de Honeywell anularán la garantía. ABRAZADERA DE RESORTE DE TERMINALES DE LA MANGUERA DE LA VÁLVULA...
  • Page 6 MS35702 Para obtener más información sobre el mantenimiento y Fig. 6. Cómo quitar la válvula de llenado existente. el reemplazo, visite http://yourhome.honeywell.com o llame al 1-800-468-1502 o al 1-800-814-9452. Paso 4 Cómo instalar una válvula de llenado nueva 1.
  • Page 7 HM700AFVALVE 33-00158EFS—01...
  • Page 8 HM700AFVALVE Soluciones de Control y Automatización Honeywell International Inc. 1985 Douglas Drive North ® Marca registrada en los Estados Unidos Golden Valley, MN 55422 © 2016 Honeywell International Inc. 33-00158EFS—01 M.S. 03-16 customer.honeywell.com Impreso en Estados Unidos...