Step
Description
11.
The master system effects the change to the "Operational" state at
the function module.
Response
l
The two−colored LED "Connection status to the standard device"
0
(
) is constantly illuminated with a green light.
l
You can read (e.g. status word) or write setpoints (e.g. frequency
setpoint) via the PDOs.
12.
Enable standard device via terminal 28 (CINH).
l
Set terminal 28 to HIGH level.
13.
Select setpoint.
l
The master sends the setpoint via the process output word
selected.
14.
Now the drive starts.
15.
Inhibit standard device.
l
Via the bus (e. g. control word bit 9), or
l
Set terminal 28 (CINH) to LOW level.
EDK82ZAFUC−001 DE/EN/FR 5.0
l
Commissioning
Commissioning steps
Detailed
information
^ 69