Commissioning steps
)
Note!
Do not change the setting sequence.
Step
Description
1.
Configure master system (CANopen master) for communication with
the function module.
2.
Inhibit standard device via terminal 28 (CINH).
l
Set terminal 28 to LOW level.
l
Later the standard device can be inhibited and enabled via the
bus.
3.
Connect mains voltage and, if available, separate voltage supply of
the function module.
l
After approx. 1 second the standard device will be ready for
operation.
l
Controller inhibit (CINH) is active.
4.
Check status display.
Response
l
The two−colored LED "Connection status to the standard device"
0
(
) is constantly illuminated with a green light .
l
The LED "Status of the CANopen communication" (
Precondition: Other nodes have to be already connected to the
bus.
l
Keypad:
EDK82ZAFUC−001 DE/EN/FR 5.0
dc
(if plugged in)
l
Commissioning
Commissioning steps
Detailed
information
^ 64
Documentation
of the standard
device
^ 68
^ 69
1
) is blinking.