16.13 Other
tbA
Alarm relay silencing: by pushing one of the keypad buttons. no= alarm relay stays
on; yES= alarm relay is switched off by pushing any keys.
OAP
Alarm relay output polarity: cL=closed when activated; oP= opened when activated
oFF
Switching ON/OFF enabling
permits the switching ON/OFF of the instrument by pressing the SET key for more than
4s.
Serial address (1 –247) It is used in monitoring system.
Adr:
Ptb
Parameter table code: readable only.
rEL
Software release for internal use.
17. TYPE DE RÉGULATION
17.1 REGULATION PRESSION DIGITAL SCROLL
La pression est ajustée par une régulation PI.
17.1.1 Démarrage régulation : capacité en augmentation
a.
La regulation démarre quand la pression d'aspiration (temperature) augmente et
attaint la valeur SET-Pbd/2+(Pbd*PM)/100. D'abord (si disponible), le compresseur
digital est allumé et module en mode PWM.
NOTE: Au demarrage, la vane est alimentée pendant SUt secondes.
A l'intérieur de la bande d'ajustement (SET–Pbd/2 ÷ SET+Pbd/2), le DSC est activé
b.
en mode PWM en function de la valeur de la variable de contrôle. (NOTE: Quand
le TRIAC est ON, le compresseur est déchargé; lorsque le TRIAC est OFF, le
compresseur fonctionne.
1593001400 XC645CX FR r1.0 01.04.2015