Télécharger Imprimer la page

Helios AIR1/KWL-CO2 0-10V Notice De Montage Et D'utilisation page 9

Publicité

Les langues disponibles

Les langues disponibles

Installation and operating instructions
ATTENTION
CHAPTER 2
DATA
NOTE
Room sensor AIR1/KWL-CO2 0-10V
Any use other than the intended use is prohibited!
2.1 Technical data
AIR1/KWL-CO2 0-10 V
Dimensions (W x H x D) mm
Power supply
Power consumption
Sensor
Measuring range
Output
Relay output
Measuring accuracy
Temperature dependence
Pressure dependence
Long-term stability
Gas exchange
Ambient temperature
Warm up time
Response time
Electrical connection
Housing
Installation
Protection class
Protection type
Standards
The recommended installation height for the room sensor AIR1/KWL-CO2 0-10 V
is between 1.4 and 1.5 m, persons who are usually standing and sitting are con-
sidered equally at this height.
The room sensor AIR1/KWL-CO2 0-10 V can also be installed at a different height
if the specific spatial conditions do not allow the recommended installation height.
85 x 85 x 27 mm
24 V AC ⁄ DC (± 10 %)
0.6 W ⁄ 24 V DC;
1.2 VA ⁄ 24 V AC;
peak current 200 mA
Optical NDIR sensor (non-dispersive infra-red
technology), with manual calibration (via zero
button), with automatic calibration (can be
deactivated via DIP switches)
0...2000 ppm or 0...5000 ppm (selectable via
DIP switches)
0 -10 V with offset potentiometer (± 10 % of
the measuring range)
potential-free changeover contact (24 V / 1 A)
± 30 ppm ± 3 % of measured value
± 5 ppm ⁄ °C or ± 0.5 % of measured value ⁄
°C (whichever is higher)
± 0.13 % ⁄ mm Hg
< 2 % in 15 years
by diffusion
0...+ 50 °C
approx. 1 hour
< 2 minutes
0.14 - 1.5 mm
, via screw terminals
2
plastic, material ABS, colour pure white (simi
lar to RAL 9010)
wall mounting or on in-wall flusch box, Ø 55
mm, base with 4-hole for
mounting on vertically or horizontally installed
in-wall flush boxes for cable entry from the
back, with predetermined breaking point for
on-wall cable entry from top ⁄ bottom in
case of plain on-wall installation
III (according to EN 60 730)
IP 30 (according to EN 60 529)
CE conformity, electromagnetic compatibili
ty according to EN 61 326, EMC Directive
2014 ⁄ 30 ⁄ EU, Low Voltage Directive
2014 ⁄ 35 ⁄ EU
2
EN

Publicité