Settings
Frequency of polarity reversal (setting with DIP switch)
Setting range
Settings
Default setting
Constructive Design
Housing
Dimensions
7XT7100-0BA00
7XT7100-0EA00
Mass
7XT7100-0BA00
7XT7100-0EA00
Degree of protection acc. to EN 60529
Housing
Terminals
Firmware version of the Protection Device 7UM
7UM515
7UM62
32
0.5 to 4.0 Hz
5 %
±
0.5 Hz, 1.0 Hz, 1.5 Hz, 2.0 Hz,
2.5 Hz, 3.0 Hz, 3.5 Hz, 4.0 Hz
1.5 Hz
7XP20, 1/6 19 inch case
312.8 mm x 75.0 mm x 243.5 mm
with Z-angles and terminal strip
266.0 mm x 75.0 mm x 235.5 mm
with terminal strip
2.3 kg
2.1 kg
IP51
IP20
≥ V3.11
≥ V4.1
SIPROTEC 4, Injection Unit 7XT71, Product Information