Copy sensor data
Reset
LEVEL TRANSMITTER 8177 • 4 ... 20 mA/HART
6 Set up with the indicating and adjustment module
Note:
Check the distance to the product surface, because if an incorrect (too
large) value is entered, the existing level will be saved as false signal.
The filling level would then no longer be detectable in this area.
This function enables reading out parameter adjustment data as well
as writing parameter adjustment data into the sensor via the indicating
and adjustment module. A description of the function is available in the
operating instructions manual "Indicating and adjustment module".
The following data are read out or written with this function:
Measured value presentation
l
Adjustment
l
Medium
l
Vessel form
l
Damping
l
Linearisation curve
l
Sensor-TAG
l
Displayed value
l
Display unit
l
Scaling
l
Current output
l
Unit of measurement
l
Language
l
The following safety-relevant data are not read out or written:
HART mode
l
PIN
l
Copy sensor data
Copy sensor data?
Basic adjustment
If the function "Reset" is carried out, the sensor resets the values of the
following menu items to the reset values (see chart):
Function
Max. adjustment
Min. adjustment
Medium
Vessel form
Damping
Linearisation
Sensor-TAG
1)
Sensor-specific basic adjustment.
2)
Depending on the sensor type, see chapter "Technical data".
1)
Reset value
0 m(d)
Meas. range end in m(d)
Liquid
not known
0 s
linear
Sensor
2)
29