Automatic shut-off takes too long or there is continuous flow
(Fig. K):
•
Clean the inside of the delay case t using a clean, dry cloth;
and clean the calibrated groove s with a non-metallic, sharp point.
•
Check that the lip seal q and seat o are in good condition.
•
AB cartridge: remember to replace the spring r.
Dripping or a constant trickle (Fig. K):
•
Clean the seat o or replace if damaged.
•
AB cartridge: remember to replace the spring r.
Fig. K: : standard cartridge
Parts of the cartridge:
: seat
o
: valve holder
Beware: do not grease the inside of the mechanism.
Mixer: regularly check (as often as necessary) the temperature selector
and the mixer's two internal seats on which the mixing key turns.
Replace as necessary.
NB: Check that the seals between wall plate and the wall and between
the wall plate and the mixer/tap/valve are watertight
at least once a year, and more often if necessary. Replace as necessary.
MAINTENANCE AND CLEANING
Cleaning chrome and stainless steel: do not use abrasive,
•
chlorine or any other acid-based cleaning products.
Clean with mild soapy water using a cloth or a sponge.
Frost protection: drain the pipes and operate the valve several times
•
to drain any remaining water. In the event of prolonged exposure
to frost, we recommend taking the mechanisms apart
and storing them indoors.
For the UK market only: Tel. 01491 821 821 - email: technical@delabie.co.uk
The installation guide is available on: www.delabie.co.uk
For all other markets: Tel. +33 (0)3 22 60 22 74 - email: sav@delabie.fr
The installation guide is available on: www.delabie.com
: lip seal
q
: spring
r
After Sales Care Support:
: AB cartridge
: calibrated groove
s
: delay case
t