4.3. CONNECTION TO HOT AIR DUCTS
4.3.1. AIR DELIVERY DUCTS
The space heater is set to operate with direct distribution of air.
Nevertheless, it can be connected to appropriately sized air
distribution channels, if required, with maximum diameter and
length as shown in the "TECHNICAL SPECIFICATION TABLE."
Warning
Before starting the heater, check that the direction of
rotation of the fan matches the direction shown on the fan
itself.
The air distribution channels can be connected by using the various
accessories supplied, placing the connector head-on to one or more
outlets chosen as needed.
4.3.2. AIR SUCTION DUCTS
The heater can be connected to suction ducts to distribute air from
the room to be heated. These ducts must comply with the maximum
diameter and length specified in the "TECHNICAL SPECIFICATION
TABLE" and must be connected with accessory (A1) (provided), to
be assembled on the centrifugal fan casing.
The centrifugal fan has a panel (B) with a sliding shutter (C) to emit
fresh air for ventilation. The shutter can be set from a minimum
value (position D) to a maximum value (position E).
Warning
Accessory (A) for connecting the air suction duct and
panel (B) with pair flow adjustment shutter (C) can be
assembled on either the right or left side of the fan casing.
4.4. MOUNTING THE DIESEL BURNER
4.4.1. RIELLO BURNER
• Open the box containing the diesel burner, remove it and keep the
two stickers with lot number for later use;
• Consult the user manual of the burner; and fit the burner fixing
screw onto the burner plate according to the instructions
• Secure the burner plate to the machine by using the 4xM8 screws
and the D8 x D24 washers;
L-L 274.00-BM
A1
B1
D1
E1
C1
EN
• Insert the burner and fix it to the plate by tightening the nut
supplied onto the screw G;
• Locate the black cable with 7-pin Wieland plug running out of the
electrical panel and insert the plug into the socket H on the
burner;
H
• Remove the burner cover and secure the two hoses to the fittings
of the fuel pump already in place;
Warning
The diesel burner is factory-set according to the
parameters shown on the "TECHNICAL SPECIFICATIONS
TABLE" for 50Hz models.
For 60Hz models, you have to change the combustion air
setting as shown on the Table.
4.4.2. ECOFLAM BURNER
• Open the box containing the diesel burner, remove it and keep the
two stickers with lot number for later use;
• Secure the burner plate to the machine by using the 4xM8 screws;
• Insert the burner and fix it to the plate by tightening the nut
supplied onto the central screw;
• Locate the black cable with 7-pin Wieland plug running out of the
electrical panel and insert the plug into the socket H on the
burner;
• The ECOFLAM burner is factory-set according to the data shown
on the Technical Specifications Table in the User Manual.
Warning
The diesel burner is factory-set according to the
parameters shown on the "TECHNICAL SPECIFICATIONS
TABLE" for 50Hz models.
For 60Hz models, you have to change the combustion air
setting as shown on the Table.
4.4.3. DIESEL FILTER
• Take the diesel filter and nipple L. Place aluminium washer N
between the connection and nipple L and screw the nipple fully
down.
Warning
The threaded portion with internal conical chamfer M
must protrude in order to allow seal tightening with the
hose.
G
M
N
L

Publicité