DESCRIPTION
ELITE 30 space heater has been designed for use in small to medi-
um-sized rooms and buildings where a fixed heating system is re-
quired.
Heat is produced by combustion and the heat from the smoke is
transmitted to the fresh air through the metal walls of the combustion
chamber and the heat exchanger. The combustion chamber is of the
type where smoke circulates twice.
The air and smoke pass through separated ducts, both of which
are welded and sealed. When, after combustion, the waste gases have
cooled, they are expelled through a duct which must be connected to a
chimney or chimney flue. The chimney or chimney flue must be big
enough to guarantee that the smoke is expelled efficiently.
The air which is used in combustion is aspirated directly from the
room or building which is being heated. It is therefore of utmost im-
portance that the room or building be properly ventilated so that
enough fresh air is circulating at all times.
The space heater is equipped with two vain (Fig.1): a front one in-
cludes the control panel (a) and the burner (b), and a back one includes
the tank (c) (only for oil version). Both compartments are accessible
removing the panels (A) (practice a light traction on the panel).
a
b
A
ELITE 30 space heater can operate with burners that are fuelled by
heating oil, methane (G20) or L.P.G. (butane G30 and propane G31) of
the ON-OFF type.
The space heater (Fig.2) is equipped with air suction grate (a) and
a heat output shutter (b), that always have to be placed on opposite
sides. The air suction grate (a) and the heat output shutter (b) can be
placed indifferently on one of the two sides.
a
c
Fig.1
b
Fig.2
Warning
Only the burners which are chosen and supplied by the
manufacturer can be used. If another type of burner is
used the heater no longer complies with CE regulations.
There are three safety devices which are activated in case of serious
malfunction. The Burner Control Device, which is mounted on the
burner and has a restart button, automatically stops the burner if the
flame goes out. The Overheat Thermostat, L, of the manual restart
type, is activated if the temperature of the combustion chamber rises
above the set maximum limit; the warning light (8) lights up and the
heater stops working. The Thermal Relay, RM, is activated if the fan
motor starts to useelectrical current than the maximum permitted limit;
the warning light (9) lights up and the heater stops working.
If any of these safety devices are activated you should check careful-
ly what the problem actually is before pressing the restart button and
starting the heater off again ("OBSERVED FAULTS, CAUSES AND
REMEDIES").
GENERAL ADVICE
The space heater must be installed, set up and used in accordance
with existing laws. Here are a few general guidelines which should be
A
followed:
• Follow the instructions in this booklet very carefully;
• Don't install the heater in places where there may be a risk of fire
or explosion;
• Inflammable material should be kept at a safe distance from the
heater (minimum 3 meters);
• All fire prevention regulations must be adhered to;
• The room or building which is being heated must be sufficiently
ventilated so that the heater has enough air to function properly;
• The heater must be near a chimney or chimney flue and a suitable
electric switchboard;
• Don't let animals or children near the heater;
• After use make sure the disconnecting switch is off;
When using any type of space heater it is obligatory:
• not to exceed the maximum level of heat output of the furnace.
• to make sure that there is adequate air circulation and air supply to the
heater and that nothing is obstructing the aspiration and expulsion of
air. Movement of air may be obstructed in various ways including plac-
ing covers or other objects on the heater or positioning the heater too
near a wall or other large object. If there is insufficient air supply the
combustion chamber overheats and the overheat thermostat with man-
ual restart is activated.
INSTALLATION
Warning
The following operations must be carried out by quali-
fied personnel only.
ELECTRICAL CONNECTIONS AND SETTINGS
Every space heater is supplied along with the safety and control
devices which are indispensable to the correct functioning of the unit.
The electric switchboard, the fan thermostat and the overheat thermo-
stat with manual restart have already been connected.
Warning
The mains supply to the heater must be earthed and
have a magneto-thermal switch with differential.
The power cord must be connected to a switch board
which has a disconnecting switch.
You still must connect the power cord having read the adhesive la-
bel which details electricity supply characteristics.
Having completed all these operations check carefully that all elec-
trical connections correspond to the wiring diagram and check the set-
ting of thermostat F ("TECNICAL SPECIFICATION"). When the heater is
first turned on you must check that the fan does not use more current
than the maximum permitted limit.