6.1.3 Connection of the power supply
line
Earth cable should be about 10mm longer
than the other two, so that it will not be
disconnected accidentally if pulled.
All signal cables must be grouped together
by means of a strap.
Connect the cables as shown in figure.
24Vac
L
a
N
Fig. 3
Standard box.
N
a
Fig. 4
UL certified box.
MNVKUPTPSUL_1423_EN
a 24Vac
OUT
IN
L
IN
Use the supplied gaskets for cables with
reduced diameters: From 3mm to 6mm.
Fig. 5
6.1.4 Connecting the light sensitive
switch for the LED illuminator
Connect the Day/Night (J5) output identified by
STATUS (+) to the alarm input (refer to the P&T
manual).
Connect the second Day/Night (J5) output identified
by STATUS to the alarms common terminal of the P&T.
6.1.5 Replacing the cable gland
The operation is only to be carried out with
UL certified versions.
Access the lower part of the Pan & Tilt base.
Disassemble the highlighted cable gland to replace
it with the provided connector, taking care not to
damage the fixing nut.
Fig. 6
5