Parameter
TRAVEL_COUNT_LIM
TRAVEL_TIME_CLOSE_OPEN
TRAVEL_TIME_OPEN_CLOSE
TRAVEL_TIME_CLOSE_
OPEN_TOL
TRAVEL_TIME_OPEN_
CLOSE_TOL
SELF_CALIB_CMD
34 - 8642
Description
Limit for TRAVEL_COUNT; at 0
TRAVEL_COUNT_LIM will not be processed.
If the LIMIT value is exceeded, the corres-
ponding bit will be set in CHECK_BACK.
Limit for the time in seconds between the
change of the state from CLOSE to
OPEN; with 0, the time is not processed.
If the value is exceeded, the corresponding
bit will be set in CHECK_BACK. Times less
than 2 seconds cannot be monitored.
Limit for the time in seconds between the
change of the state from OPEN to
CLOSE; with 0, the time is not processed.
If the value is exceeded, the corresponding
bit will be set in CHECK_BACK. Times less
than 2 seconds cannot be monitored.
Maximum difference between
TRAVEL_TIME_CLOSE_OPEN and the
current switching time
Maximum difference between
TRAVEL_TIME_OPEN_CLOSE and the
current switching time
Initiation of a device-specific calibration
procedure, manufacturer specific 0-default.
y = 0
active undamped
y = 1
active damped
x = 0
sensor indicates "valve open"
x = 1
sensor indicates "valve closed"
x y