5.3.2.3 Output current value 20mA
Parameter:
P11
Menu path:
OUTPUT SETUP / ANALOG OUTPUT / 20mA VALUE
Description:
Measured value assigned to 20mA.
The transmitted value is in accordance to the primary value (PV) (P01:a). Assignment can
be done that the change in measured value and the change in the output value are the
same (normal), or opposite directional (inverse operation). For example: 1m level is 4 mA,
10m level is 20mA, or 1m level is 20mA and 10m level is 4mA.
5.3.2.4 Output current error mode
Parameter:
P12:a, where a: 0, 1, 2
Menu path:
OUTPUT SETUP / ANALOG OUTPUT / ERROR MODE
Description:
Error indication by the current output
Warning This error indication is active unless the failure is fixed, or until the failure
terminates.
5.3.2.5 Fixed output current
Parameter:
P08
Menu path:
OUTPUT SETUP / ANALOG OUTPUT / MANUAL VALUE
Description:
Parameter for setting the fixed output current
Values between 3.8 and 20.5 can be entered. The output current will be set to the entered
value and analogue transmission will be suspended (see: 5.3.2.1). This error indication
overrides all other error indication.
26 / 36 mba5052i0600p_06 ♦ BKI16ATEX0012X ♦ IEC Ex BKI 12.0002♦ FM16US0068X♦ FM16CA0037X
HOLD
Error indication has no effect on the output current.
3.8 mA Error indication: the output current gets 3.8mA.
22mA
Error indication: the output current gets 22mA.
Default value:
Active measurement range (mm)
Default value:
HOLD
Default value:
4 mA