5.3.1.3 Damping time
Parameter:
P20
Menu path:
BASIC SETUP / DAMPING TIME
Description:
Damping time is used to damp the unwanted fluctuations of the output and display.
If the measured value changes rapidly the new value will settle with 1% accuracy after this
set time. (damping according to an exponential function).
5.3.2. Analogue Output
5.3.2.1 Output current mode
Parameter:
P12:b, where a: 0, 1.
Menu path:
OUTPUT SETUP / ANALOG OUTPUT / CURRENT MODE
Description:
Transmission mode of the current output [AUTO, MANUAL]
AUTO
MANUAL The output current is fixed at a constant (set) value (see 5.3.2.5). In this
5.3.2.2 Output current value 4mA
Parameter:
P10
Menu path:
OUTPUT SETUP / ANALOG OUTPUT / 4mA VALUE
Description:
Measured value assigned to 4mA.
The transmitted value is in accordance to the primary value (PV) (P01:a). Assignment can
be done that the change in measured value and the change in the output value are the
same (normal), or opposite directional (inverse operation). For example: 1m level is 4 mA,
10m level is 20mA, or 1m level is 20mA and 10m level is 4mA.
The output current is calculated from the measured value, output is
active.
mode the setting of the error current is irrelevant. The set (current) value
overwrites the 4mA output of HART multidrop mode!
FM16CA0037X ♦ FM16US0068X ♦ IEC Ex BKI 12.0002 ♦ BKI16ATEX0012X ♦ mba5052i0600p_06 ♦ 25 / 36
Default value:
0 sec
Default value:
AUTO
Default value:
0 mm