Troubleshooting

Fault
Cause
The remote con-
Starter battery is flat.
trol does not come
Power cable is disconnected or the plug
on when the
is removed.
on/off switch is
pressed.
Generator earth cable is disconnected or
the fuse (if available) is blown.
The starter does
Starter battery is flat.
not work when the
The main switch is at "0".
start button is
pressed.
Starter shaft is dirty.
Too much oil in the engine.
Inverter is damaged.
Power cable is disconnected or the plug
is removed.
Generator earth cable is disconnected or
the fuse (if available) is blown.
Starter is not receiving any power.
The starter turns
No petrol/LPG.
but the generator
Spark plug is not receiving any power.
does not start.
Carburettor is not receiving any petrol.
Air intake is blocked.
The ambient temperature is below 0 °C.
Inverter is damaged.
Power cable is disconnected or the plug
is removed.
EN
Troubleshooting
Remedy
➤ Charge the starter battery.
➤ Contact an authorised workshop.
➤ Charge the starter battery.
➤ Set the main switch to "I" or "1".
➤ Clean the starter shaft.
➤ Drain the oil.
➤ Contact an authorised workshop.
➤ Fill up with petrol/LPG.
➤ Check the electric connections.
➤ Clean the carburettor.
➤ Check the air filter (see chapter
"Servicing the air filter (fig. 7,
page 6)" on page 27).
➤ Use pure propane gas.
➤ Contact an authorised workshop.