Parameter Table - Helios ETR Instructions D'installation Et D'utilisation

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Installation and Operating Specification ETR

7.5 Parameter table

Parameter
Factory setting
Mode
27.1 °C
Actual Value
(80.8 °F)
Setpoint 1
Uout
Resistor
2049 Ω
ETR
Setpoint 1
Setpoint 2
Pband
Min. Uout
Max. Uout
Mode
Units
KTY81-210 KTY81-210
Sensortype
-50.0 °C
Range min. Tem-
perature
(-58.0 °F)
L-BAL-E293-GB 1841 Index 001
2.00
2.01
INFO
27.1 °C
(80.8 °F)
20.0 °C
-
(68.0 °F)
5.0 V
5.0 V
2049 Ω
1.00
1.00
SETTING
20.0 °C
-
(68.0 °F)
15.0 °C
-
(59.0 °F)
5.0 K
-
(9.0 °F)
0.0 V
0.0 V
10.0 V
10.0 V
BASE SETUP
2.00
2.01
°C
°C
-
User Set-
Function
ting
Mode
Display actual temperature
Display active Setpoint
Magnitude of the output voltage 0...10 V
current resistance value of the temperature
sensor
Software version
Setpoint1
Setting range:
-50.0...150.0 °C
Factory setting:
20.0 °C
Setpoint 2 active, if voltage at terminals 1, 2
Setting range:
-50.0...150.0 °C
Factory setting:
15.0 °C
Pband
Setting range:
1.0...50.0 K
Factory setting:
5.0 K
(9.0 °F)
Setting minimal output voltage
Setting maximal output voltage
Mode selection
Setting range: °C / °F
Setting type of sensor: KTY81-210 or
PT1000
Setting measuring range, minimum temper-
ature value
Setting range:
-50.0...150.0 °C
Factory setting:
-50.0 °C
Part.-No.
12/19
Programming
(-58.0...302.0 °F)
(68.0 °F)
(-58.0...302.0 °F)
(59.0 °F)
(1.8...90.0 °F)
(-58.0...302.0 °F)
(-58.0 °F)