13. Error Indications
With the procedures below, most errors can be quickly identified. If an error cannot be resolved, please refer to your
Victron Energy supplier.
13.1 General error indications
Problem
No output voltage on
MultiPlus-II GX in inverter mode
AC-out-2.
Multi will not switch over
Circuit breaker or fuse in the AC-in input is
to generator or mains
open as a result of overload.
operation.
Inverter operation not
The battery voltage is excessively high or
initiated when switched
too low. No voltage on DC connection.
on.
'Low battery'
The battery voltage is low.
The converter switches off because the
'Low battery' (Shutdown)
battery voltage is too low.
The converter load is higher than the
'Overload'
nominal load.
The converter is switched off due to
'Overload' (Shutdown)
excessively high load.
The environmental temperature is high, or
'Over Temperature'
the load is too high.
'Low Bat V Overload'
Low battery voltage and excessively high
(Shutdown)
load.
Ripple voltage on the DC connection
'High DC Ripple'
exceeds 1,5Vrms.
The inverter is switched off due to an
'DC Ripple Shutdown'
excessively high ripple voltage on the
input.
The charger does not
The AC input voltage or frequency is not
operate.
within the range set.
Circuit breaker or fuse in the AC-in input is
open as a result of overload.
The battery fuse has blown.
The distortion or the AC input voltage is
too large (generally generator supply).
MultiPlus-II GX is in 'Bulk protection' mode
The charger does not
thus, the maximum bulk charging time of
operate. 'Bulk Protection'
10 hours is exceeded. Such a long
shown.
charging time could indicate a system
error (e.g. a battery cell short-circuit).
The battery is not
Charging current excessively high,
completely charged.
causing premature absorption phase.
Poor battery connection.
The absorption voltage has been set to an
incorrect level (too low).
The float voltage has been set to an
incorrect level (too low).
The available charging time is too short to
fully charge the battery.
Cause
Remove overload or short circuit on AC-
out-1 or AC-out-2, and reset fuse/breaker.
Ensure that the battery voltage is within
the correct range.
Charge the battery or check the battery
connections.
Charge the battery or check the battery
connections.
Reduce the load.
Reduce the load.
Install the converter in cool and well-
ventilated environment, or reduce the load.
Charge the batteries, disconnect or reduce
the load, or install higher capacity batteries.
Fit shorter and/or thicker battery cables.
Check the battery cables and battery
connections. Check whether battery
capacity is sufficiently high, and increase
this if necessary.
Install batteries with a larger capacity. Fit
shorter and/or thicker battery cables, and
reset the inverter (switch off, and then on
again).
Ensure that the AC input is between
185VAC and 265VAC, and that the
frequency is within the range set (default
setting 45-65 Hz).
Remove overload or short circuit on AC-
out-1 or AC-out-2, and reset fuse/breaker.
Replace the battery fuse.
Turn the settings WeakAC and dynamic
current limiter on.
Check your batteries. NOTE: You can reset
the error mode by switching off and back
on the MultiPlus-II GX. The standard
MultiPlus-II GX factory setting of the 'Bulk
protection' mode is switched on. The 'Bulk
protection' mode can be switched off with
help of VEConfigure only.
Set the charging current to a level between
0.1 and 0.2 times the battery capacity.
Check the battery connections.
Set the absorption voltage to the correct
level.
Set the float voltage to the correct level.
Select a longer charging time or higher
charging current.
Solution
15