Alcove Installation; Floor Protection; Outside Air - Napoleon S1 Instructions D'installation Et D'utilisation

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Clearances can be reduced with shielding acceptable to local authorities. Reduced installation must comply
with NFPA 211 or CAN/CSA-B365.
10
Clearances are unable to be reduced for the 1150 by using double wall pipe.
3.3

ALCOVE INSTALLATION

3.3
ALCOVE INSTALLATION
1100 series only may be installed, using a listed double wall connector,
S1 and S4 models only may be installed, using a listed double wall
such as Security DL6 in Canada, the Simpson Duravent Plus DVL in
EN
connector, such as Security DL6 in Canada, the Simpson DuraVent Plus
the USA or an equivalent double wall connector, into an alcove having
DVL in the USA, or an equivalent double wall connector, into an alcove
a depth of no more than 4 feet and a height of at least 7 feet (2.1m).
having a depth of no more than 4 feet and a height of at least 7 feet
The minimum clearances are as shown.
(2.1m). The minimum clearances are as shown.
* Double wall connector clearances are as per the connector manufacturer's instructions.
3.4

FLOOR PROTECTION

EMBER PROTECTOR:
This appliance must be installed on a non-combustible protector that extends to the front, sides and back of the
appliance as per the minimum requirements below.
NOTE: Ember protection is required for spark and ash shielding, not for limiting fl oor temperatures
from the radiant heat of the appliance. The appliance was designed and safety tested so that without
any protection, the fl oor will not overheat.
L
J
I
3.5

OUTSIDE AIR

IF ROOM AIR STARVATION OCCURS BECAUSE THE FRESH AIR INTAKE IS BLOCKED WITH ICE,
LEAVES, ETC., OR BECAUSE THE APPLIANCE DOOR WAS LEFT OPEN, OR DUE TO A STRONG
EXHAUST FAN OPERATING ETC., DANGEROUS FUMES AND SMOKE FROM THE OPERATING
The following are signs that a fresh air kit may be required:
When there is combustion present: Wood burns poorly, smoke spills, back-draft takes place and your
chimney does not draw steadily.
In the winter there is too much condensation on the windows.
Opening a window seems to alleviate the above symptoms.
A ventilation system is installed in the house.
Other devices are present that exhaust house air.
The house has tight fitting windows and/or is equipped with a well-sealed vapour barrier.
If possible connect the air intake at the pedestal's back to outside air with a 4 inch (100mm) diameter fresh
air kit available at your authorized dealer / distributor. Follow detailed instructions under "Mobile Home
Outside Air".
W415-1476 / D / 08.21.18
L
K
J
J
J
CANADA
18" (45.7cm)
USA
16" (40.6cm)
I
APPLIANCE COULD BE DRAWN INTO THE ROOM.
MINIMUM FLOOR PROTECTION
FRONT (I)
SIDES (J)
8" (203.2mm)
8" (203.2mm)
WARNING
!
*
9"
6"
4 FOOT
14"
*
23"
ALCOVE
W415-1468 / A / 09.30.16
BACK (K)
VENT (L)
8" (203.2mm)
N/A
8" (203.2mm)
2" (50.8mm)
99.1B
FEET
MAX

Publicité

Chapitres

Table des Matières
loading

Ce manuel est également adapté pour:

S4S9

Table des Matières