Télécharger Imprimer la page

Frico PAEC3200C Serie Manuel D'instructions page 4

Masquer les pouces Voir aussi pour PAEC3200C Serie:

Publicité

Les langues disponibles

Les langues disponibles

Output charts water PAEC3200CW
Metric chart
Type
Fan
position
PAEC3210CW-NA max
PAEC3215CW-NA max
PAEC3220CW-NA max
Type
Fan
position
PAEC3210CW-NA max
PAEC3215CW-NA max
PAEC3220CW-NA max
*
) Recommended outlet air temperature for good comfort and optimized output.
1
*
) Nominal output at given supply and return water temperature.
2
Imperial chart
Type
Fan
position
PAEC3210CW-NA max
PAEC3215CW-NA max
PAEC3220CW-NA max
Type
Fan
position
PAEC3210CW-NA max
PAEC3215CW-NA max
PAEC3220CW-NA max
*
) Recommended outlet air temperature for good comfort and optimized output.
1
*
) Nominal output at given supply and return water temperature.
2
4
PAEC3200C
Supply water temperature:80 °C
Room temperature: +18 °C
Outlet air temperature: +35 °C*
Airflow
Output
Return
water temp.
[m
/h]
[kW]
[°C]
3
1460
10.0
42
2150
15.3
38
2920
21.2
38
Supply water temperature: 60 °C
Room temperature: +18 °C
Outlet air temperature: +35 °C*
Airflow
Output
Return
water temp.
[m
/h]
[kW]
[°C]
3
1460
10.2
48
2150
14.6
42
2920
21.6
45
Supply water temperature:176 °F
Room temperature: +64 °F
Outlet air temperature: +95 °F*
Airflow
Output
Return
water temp.
[cfm]
[MBH]
[°F]
1050
34.1
108
1550
52.2
100
2150
72.4
100
Supply water temperature: 140 °F
Room temperature: +64 °F
Outlet air temperature: +95 °F*
Airflow
Output
Return
water temp.
[cfm]
[MBH]
[°F]
1050
34.8
118
1550
49.8
108
2150
73.7
113
Water temperature: 80/60 °C
Room temperature: +18 °C
1
Water
Pressure
Output*
flow
drop
[l/s]
[kPa]
[kW]
0.06
1.4
14.9
0.09
2.0
24.2
0.12
2.6
33.4
Water temperature: 60/40 °C
Room temperature: +18 °C
1
Water
Pressure
Output*
flow
drop
[l/s]
[kPa]
[kW]
0.20
10.9
8.2
0.20
8.7
13.6
0.35
17.2
18.9
Water temperature: 176/140 °F
Room temperature: +64 °F
1
Water
Pressure
Output*
flow
drop
[US gal/h]
[kPa]
[MBH]
61.3
1.4
50.9
84.6
2.0
82.6
117.9
2.6
114.0
Water temperature: 140/104 °F
Room temperature: +64 °F
1
Water
Pressure
Output*
flow
drop
[US gal/h]
[kPa]
[MBH]
188.3
10.9
28.0
193.1
8.7
46.4
331.9
17.2
64.5
Outlet
Water
Pressure
2
air temp.
flow
drop
[°C]
[l/s]
[kPa]
42
0.18
8.8
45
0.30
16.2
44
0.41
21.6
Outlet
Water
Pressure
2
air temp.
flow
drop
[°C]
[l/s]
[kPa]
32
0.10
3.2
33
0.17
6.1
33
0.23
8.1
Outlet
Water
Pressure
2
air temp.
flow
drop
[°F]
[US gal/h]
[kPa]
108
173.1
8.8
113
280.6
16.2
111
388.1
21.6
Outlet
Water
Pressure
2
air temp.
flow
drop
[°F]
[US gal/h]
[kPa]
90
94.0
3.2
91
156.9
6.1
91
217.8
8.1

Publicité

loading