PREMASGARD
Function 06 Write Single Register &
Function 16 Write Multiple Register
Register
Parameter (display)
4x0023
k factor
4x0024
Function type
Note on k factor (register 4x0023)
The computed coefficients for the volume flow display are not saved in the permanent memory
and are lost at zero voltage. They must be reset when the communication begins.
If the k factor of the manufacturer of the fan is provided in the SI unit system, the value can be applied directly.
If specified in the Imperial System of Units, the k-factor must be multiplied by the factor of 9.2846.
Selection of the function type (register 4x0024)
Type 1:
Rosenberg, Comefri,
Gebhardt Nicotra
Type 2:
Ziehl-Abegg,
EBM Papst
Type 3:
Fläkt Woods
Function 08 Diagnostics
The following sub function codes are supported
Sub Function
Parameter
Code
00
Echo of transmission data
(Loopback)
01
Restart Modbus
(Reset listen-only mode)
04
Activation listen-only mode
10
Delete counter
11
Counter bus telegrams
12
Counter communication errors
(Parity, CRC, frame errors, etc.)
13
Counter exception telegrams
14
Counter slave telegrams
15
Counter telegrams without answer
Function 17 Report Slave ID
Composition of answer telegram
Byte No.
Parameter
00
Number of bytes
01
Slave ID (device type)
02
Slave ID (device class)
03
Status
04
Version number (release)
05
Version number (version)
06
Version number (index)
724x - Modbus | Telegrams
Data Type
Unsigned 16 Bit
1...2000
Unsigned 8 Bit
1...3
3
= Volume flow [m
/h]
= k factor
= Differential pressure of the static pressures [Pa]
3
= Air density [kg/m
]
Data Type
Answer
Echo data
Echo telegram
No answer
Echo telegram
Unsigned 16 Bit
All valid bus telegrams
Unsigned 16 Bit
Faulty bus telegrams
Unsigned 16 Bit
Error counter
Unsigned 16 Bit
Slave telegrams
Unsigned 16 Bit
Broadcast messages (address 0)
Data Type
Answer
Unsigned 8 Bit
6
18 = PREMASGARD
Unsigned 8 Bit
Unsigned 8 Bit
30 = PREMASGARD
Unsigned 8 Bit
255 = RUN, 0 = STOP
Unsigned 8 Bit
1...9
Unsigned 8 Bit
1...99
Unsigned 8 Bit
1
22
Value
Range
1...2000
1...3
®
724x
®
/ PREMASREG
®