Télécharger Imprimer la page

S+S Regeltechnik PREMASGARD 724x - Modbus Notice D'instruction page 14

Publicité

Les langues disponibles

Les langues disponibles

G
®
PREMASGARD
Maintenance-free, microprocessor-controlled PREMASGARD
optionally with ⁄ without display, with cable gland  or M12 connector according to DIN EN 61076-2-101, for measuring the differential pressure (max.
–7000...+7000 Pa) in air. Incl. connection set ASD-06 (2 m connecting hose, two pressure port nipples, screws). Type variant 724x T with connection
facility for external Pt1000 sensor (sensor element not included in the scope of delivery) for detecting the temperature (–50...+150°C).
The standard display can be changed from SI [Pa, m
The pressure sensor is applied to measure positive, negative or differential pressure in clean air and gaseous media. It is used in the clean room,
medical and filter technology, ventilation and air conditioning ducts, spray booths, large-scale catering facilities, for filter monitoring and level measure-
ment or for triggering frequency converters. A pressure sensor with piezoresistive measuring element guarantees exact measurement results.
The following measured values can be accessed via the Modbus: Differential pressure, volume flow and temperature.
Innovative Modbus sensor with galvanically separated RS485 Modbus interface, selectable bus termination resistance, DIP switch for setting the
bus parameters and bus address in current-free state, LEDs for telegram status display, two separate push-in terminals and large three-line display
(illuminated; with customised programming in the 7-segment and dot-matrix range). The sensor is factory-calibrated; an environmental precision
adjustment by an expert is possible.
TECHNICAL DATA
Power supply:
Power consumption:
Pressure type:
Data points:
System of units:
Measuring range, pressure:
Pressure accuracy:
Above- ⁄ below-pressure:
Zero point offset:
Hysteresis:
Linearity:
Temp. drift values:
Long-term stability:
Bus protocol:
Signal filtering:
Pressure connection:
Medium:
Media contacting parts:
Media temperature:
Ambient temperature:
Permissible humidity:
Electrical connection:
Housing:
Housing dimensions:
Cable connection:
Protection class:
Safety class:
Standards:
Optional:
ACCESSORIES
ASD - 06
724x - Modbus
3
/h, °C] to imperial units [inWC, CFM, °F] via Modbus.
24 V AC (± 20 %) and 15...36 V DC
< 4.8 W ⁄ 24 V DC typical; < 6.8 VA ⁄ 24 V AC typical
differential pressure (2 measuring channels)
differential pressure [Pa], volume flow [m
temperature [°C] – Type 724x T with connection facility for external Pt1000 sensor (–50...+150°C)
(sensor element not included in the scope of delivery)
SI [Pa, m
3
/h, °C] or imperial [inWC, CFM, °F] (can be changed via Modbus)
–500... +500 Pa or
–7000...+7000 Pa
depending on the device type, see table
Type 7249 (500 Pa): typical ± 13 Pa
Type 724x (7000 Pa): typical ± 105 Pa
compared to a calibrated reference device
max. ± 50 kPa
± 10 % measuring range
0.3 % of final value
< ± 1 % of final value
± 0.1 % ⁄ °C
± 1 % per year
Modbus (RTU mode), address range 0...247 selectable
0 s / 1 s / 10 s at pressure (4 s / 32 s at temperature)
with nozzles for pressure hose Ø 6 mm
clean air and non-aggressive, non-combustible gases
brass, Ni, Duroplast, Si, epoxy, RTV, BSG, UV silicone gel
–20...+50°C (temperature-compensated 0...+50°C)
–30...+70 °C
0...95 % r. H. (non-precipitating air)
0.2 - 1.5 mm
2
, via push-in terminals
plastic, UV-resistant, polyamide material, 30% glass-globe reinforced,
with quick-locking screws (slotted ⁄ Phillips head combination),
colour traffic white (similar to RAL 9016), housing cover for display is transparent!
126 x 90 x 50 mm (Tyr 2)
cable gland plastic (M 16 x 1.5;
with strain relief, exchangeable, inner diameter 10.4 mm) or
M12 connector according to DIN EN 61076-2-101
III (according to EN 60 730)
IP 65 (according to EN 60 529) in the built-in state
CE-conformity, electromagnetic compatibility according to EN 61 326, EMC directive 2014 ⁄ 30 ⁄ EU
display with illumination, 3-line, programmable, cut-out approx. 70 x 40 mm (W x H),
to display the ACTUAL pressure of both channels or the ACTUAL temperature (cyclic)
or an individually programmable display value
see table
connection set (nipple straight) (included in the scope of delivery)
®
724x - Modbus (series) with Modbus connection, impact-resistant plastic housing,
3
/h],
14
Rev. 2022 - V12

Publicité

loading