OTHER DISPLAYS:
Lvd
LVD – low voltage load disconnect (load only)
Hvd
High voltage disconnect (both solar and load)
Hot
High temperature disconnect (both solar and load)
OCP
Overcurrent and short circuit protection (load, solar overcurrent)
O.O
Short circuit protection (solar only)
SELF-DIAGNOSTICS (SELF-TEST)
Push button and hold down for 4 seconds.
NOTE: The push button can be used to toggle through the
displays faster.The entire self-test takes 30 to 45 seconds.
The load will be turned on for 0.1 second and may flash
during the test. A short or overload condition could
cause a controller restart.
The following displays will occur (examples are used):
8.8.8
Self-test started, checking the digital meter segments
12u
The system voltage (12/24/48)
15A
ProStar current rating
1.5
Software version installed
r
E04
A fault has been detected (see list below)
---
Display if no fault is found
25c
Temperature measured at the controller
rP
Remote temp probe is detected (if connected)
25c
Temperature at the remote probe (if connected)
SEn
Battery sense detected (if connected)
S-1
Battery select position (1, 2, or 3)
J-1
Telecom noise jumper cut (change to on-off regulation)
End
End of the self-test
End---End
Display continue if no error was detected.
End End
Display continues if an error has been detected.
To terminate the self-test, push the button. The self-test can be
repeated to confirm the result.
Error list:
E01
Rotary switch battery selection failure
E03
Voltage reference test failed (circuit, malfunctions)
E04
Solar array current fault (circuit, FETs)
E07
Load FETs off test (load connection, FETs shorted)
7