Quick commissioning

Quick commissioning allows the user to get started in the shortest possible time.
The grayed-out parameters can be overlooked as the VSD will calculate a value or use the factory default values. We suggest to check
the setting values before the VSD is put into service.
Parameter
P0010
1 = Quick commissioning
P0100
0 = kW / 50 Hz
1 = hp / 60 Hz
2 = kW / 60 Hz
P0304
10 - 2000 V
P0305
0 ... 10,000 I/nom
P0307
0 - 2000 kW
P0310
12 - 650 Hz
P0311
0 - 40000 1/min
P0700[2]
Index 0: Auto
Index I : Hand
P1000[2]
Index 0: Auto
Index I : Hand
P1080
P1082
P1120
P1121
P3900
• Press
until display reads: r0000
• Press P: display shows motor present frequency
First start-up
Default
Set to
0
1
Start quick commissioning
P0010 must always be set back to "0" before operating the motor. However,
if P3900 is set = 1 after commissioning, this operation is carried out auto-
matically.
0
0
For use in Europe / N. America
Set 0 and 1 with DIP switch 2
Set 2 with P0100
230
See burner
Motor rated voltage
manual
Motor rated voltage (V) from rating plate.
3.25
See burner
Motor rated current
manual
Motor rated current (A) from rating plate.
0.75
See burner
Motor rated power
manual
Motor rated power (kW) from rating plate. If P0100 = 1, values will be in hp.
50.00
See burner
Motor rated frequency
manual
Motor rated frequency (Hz) from rating plate.
0
See burner
Motor rated speed
manual
Motor rated speed (rpm) from rating plate.
Selection of command source (on / off)
2
2
1 = BOP Basic Operator Panel
1
1
2 = Terminal / digital inputs
Selection of frequency setpoint
2
2
1 = BOP Basic Operator Panel
1
1
2 = Analogue setpoint (default)
10.00
Min. motor frequency (0 - 650 Hz): Sets the minimum motor frequency at
0
which the motor will run, irrespective of the frequency setpoint. The value
set here is valid for both clockwise and anticlockwise rotation.
50.00
Max. motor frequency (0 - 650 Hz): Sets the maximum motor frequency at
52,5
which the motor will run, irrespective of the frequency setpoint.
The value set here is valid for both clockwise and anticlockwise rotation (do
not set this value frequently higher than 50 Hz unless the motor can be used
at higher frequencies).
10
Ramp-up time(0 - 650 s): Time it takes the motor to accelerate from stand-
40
still up to maximum motor frequency.
30
Ramp-down time(0 - 650 s): Time it takes the motor to decelerate from
40
maximum motor frequency down to standstill.
0
1
End quick commissioning
0
1
2
3
= End without motor calculation or factory values reset
= End with motor calculation and factory values reset (recommended)
= End without parameters and I/O reset
= End with I/O reset
11