Marker arrow
Rotary shutt-off cap
3
Accessories
Dial Thermometer
3.1
Figure T5100 150 00
Remove rotary shut-off cap and insert ther-
mometer into the provided hole as far as it
will go.
To relay the temperature to a building ser-
vices control system, a Pt 1000 temperature
sensor, instead of the thermometer, can be
inserted in the hole.
Filling and drain valve:
3.2
Figure J7109 173 00
(For 1/2" hose with 3/4" union nut) Unscrew
plug from drainage connection. Screw drain
valve into place and tighten.
Turn adjustable ring on drain valve to „Zu"
(Closed) position (clockwise). For drainage,
connect hose and turn to „Auf" (Open) po-
sition.
Locking screw M5
© www.kemper-olpe.de – 08.2021 / K410014000008-00 – 9 / 36
Adjusting cap
Insulating shell:
3.3
Figure 471 11
Material: PE material, fire safety class B1 to
DIN 4102, Part 1.
The one-piece, closable insulating shell can be
fastened by means of the clips included in the
scope of supply or cemented in place using
commercially available adhesive.
Temperature sensor Pt 1000:
3.4
Figure T5100 140 00
Pt 1000, T = 0 - 100 °C
4-conductor
tolerance class A
connection 2 m, 4 x 0,35 mm²
pre-assembled
Balancing head
Plug
Hex key size 2,5 mm