G e n e r a l i n f o r m a t i o n :
LW4/5 incorporate a Hall-Sensor to measure liquid level of refrigerants and oil
in liquid receivers, oil separators, flash tank and oil reservoirs. A magnetic float
changes its position according to the liquid level. The hall sensor converts these
magnetic field changes into an equivalent signal, which is used by the internal
electronic to show with the LEDs the status of liquid level. If the level reaches
certain level range (high or low level range), LW illuminates RED LED and
activate a SPDT contact. If the liquid level comes back to normal level range, the
Green LED illuminates and the contact switch back.
Notes:
LW4 is developed for HFC refrigerants, subcritical CO
3
oil (density range: 700...1300 kg/m
).
LW5 is specially adapted to the requirements of transcritical CO
and released only with dedicated adapters (Part No.:
O v e r v i e w L W 4 ... / L W 5 ... : ( s e e F i g . 1 )
LW4...
LW5...
Base unit
(60 bar)
(130 bar)
HFC, CO
&
2
Refrigerant
CO
2
HFO blend
Sight glass
High Pressure
33,3x2,4W (2)
O-ring
33,3x2,4V (4)
Sight glass
(3)
(5)
Washers (6)
3 pieces
-
Fastening
3 screws
2 screws
screws (7)
M6x45
M6x45
Fastening
1 countersunk
-
screws (8)
screw M6x45
Connection
type
OM0-CCA
LW0-CCA CO2
Adapter type
Connection size 3/4"-14 NPTF
3/4"-14 NPTF
Part No.
805039
805254
Main part
Aluminum screw adapter (11)
Aluminum
Second part
Steel flange (14)
flange (14)
High pressure
O-Ring (10)
25.07x2.62W
25.07x2.62V
Sealing parts
Tapered thread (Teflon tape)
to Vessel
Note: The numbers in brackets correspond to legends of Fig. 1.
Emerson Climate Technologies GmbH
Am Borsigturm 31 I 13507 Berlin I Germany
Liquid Level Monitoring Systems LW4/LW5 Low or High Level
S y s t e m c o m p o n e n t s :
Legend Description
1
Base unit
2
Sight glass O-ring LW4...
3
Sight glass LW4...
4
Sight glass O-ring LW5...
5
Sight glass LW5...
6
Spring washer: 3 pcs (LW4...)
, HFO blends and
2
7
Screws (M6 x 45)
Countersunk screw: 1pcs
systems
8
2
(LW5...)
805254 and 805257).
9
Screw transport holder (discard)
10
Adapter front O-ring:
Note: For details, see table below and Fig. 1
LW4...
LW5...
(60 bar)
(130 bar)
HFC, CO
&
2
CO
2
HFO blend
High Pressure
33,3x2,4W (2)
33,3x2,4V (4)
(3)
(5)
3 pieces
-
3 screws
2 screws
M6x45
M6x45
1 countersunk
-
screw M6x45
Thread NPTF
LW0-1/2
LW0-1/2 CO2
1/2"-14 NPTF
1/2"-14 NPTF
805256
805257
Aluminum
Steel flange (14)
flange (14)
High pressure
25.07x2.62W
25.07x2.62V
O-ring 28.3x1.78W (13)
*) 3 or 4 pieces M6 screws for fastening is not part of delivery.
www.emersonclimate.eu
Operating instruction
Control
Legend Description
11 / 12 Adapter with thread connection
13
Adapter O-ring backside
Flange ring
14
Aluminium (LW4...) /
Steel (LW5...)
15
Rotalock adapter
16
gasket Rotalock adapter backside
17
Flange adapter
18
Flange adapter O-ring backside
Power supply connector
19
LW-24V-x
20
Relay connector OM3-Nxx
LW4...
LW4...
(60 bar)
(60 bar)
HFC, CO
& HFO blend
2
33,3x2,4W (2)
33,3x2,4W (2)
(3)
(3)
3 pieces
3 pieces
3 screws M6x45
3 screws M6x45
-
-
Thread UNF/UNEF
OM0-CBB
OM0-CCB
1-1/8"-18 UNEF
1-1/8"-12 UNF
805038
805040
Aluminum screw adapter (12)
Aluminum flange (14)
25.07x2.62W
O-ring 21.89x2.62W (13)
Date: 25.07.2019
F i g . 1
LW4...
LW4...
(60 bar)
(60 bar)
HFC, CO
& HFO blend
2
33,3x2,4W (2)
33,3x2,4W (2)
(3)
(3)
3 pieces
3 pieces
3 screws M6x45
3 screws M6x45
-
-
Rotalock
OM0-CCD
OM0-CCE
1-3/4"-12 UNF
1-1/4"-12 UNF
805042
805043
Aluminum nut and flange (15)
-
-
25.07x2.62W
Gasket PTFE 1-3/4" (16)
Gasket PTFE 1-1/4" (16)
LW4...
(60 bar)
HFC, CO
& HFO blend
2
33,3x2,4W (2)
(3)
3 pieces
3 screws M6x45
-
Flange
OM0-CUA *
3- / 4-holes
805037
Aluminum flange (17)
-
25,07x2,62W
O-ring 33,3x2,4W (18)
LW45_OI_ML_R05_865912.docx

Publicité

loading

Sommaire des Matières pour Emerson LW4

  • Page 1 G e n e r a l i n f o r m a t i o n : S y s t e m c o m p o n e n t s : F i g . 1 LW4/5 incorporate a Hall-Sensor to measure liquid level of refrigerants and oil Legend Description Legend Description in liquid receivers, oil separators, flash tank and oil reservoirs.
  • Page 2 ½ turns until reaching the dedicated torque of 12 Nm. This procedure is • In a severely contaminated system, avoid breathing acid vapors and Connect LW-24V-x (19) and OM3-Nxx (20) cable assemblies to LW4/5 (Fig. 2). mandatory to achieve full leak tightness. avoid contact with skin from contaminated refrigerant / lubricants.
  • Page 3 OFF cycles by other means in order to prevent any false signal due to migration of liquid from or into vessel. Note2: LW4X-… and LW5X-… are calibrated differently to LW4-… and LW5-…and intended to be used with very narrow (1/2”, 12 mm) connection to vessel.
  • Page 4 B e s c h r e i b u n g : S y s t e m K o m p o n e n t e n : F i g . 1 LW4/5 messen den Flüssigkeitsstand in Kühlmittel- und Ölsammlern, Legende Beschreibung Legende Beschreibung Ölabscheidern und Flashtanks mittels eines Hall-Sensors.
  • Page 5 Der Einbau darf gemäß EN 13313 nur von Fachkräften vorgenommen Hinweis: Für einwandfreie Funktion Reglereinheit exakt horizontal werden. Konfektionierte Anschlusskabel LW-24V-x (19) und OM3-Nxx (20) an LW4/5 montieren. Dafür den Adapterring (14) drehen. (Fig. 1,2). • Bei Anlagen, in denen eine starke chemische Zersetzung stattgefunden gem.
  • Page 6 Flüssigkeit aus oder in den Behälter). Es wird empfohlen das Relais bei Nichtbetrieb zu trennen. Falsche Signale durch ein- oder ausfließende Flüssigkeit am Behälter werden dadurch verhindert. Hinweis 2: LW4X-… und LW5X-… sind anders kalibriert wie LW4-… und LW5-…und für einen schmalen Anschluss (1/2”, 12 mm) zum Behälter bestimmt. Emerson Climate Technologies GmbH www.emersonclimate.eu...
  • Page 7 C o m p o s a n t s d u s y s t è m e : Fig. 1 Les LW4/5 utilisent un capteur à effet hall pour mesurer les niveaux de liquide Légende Description Légende Description réfrigérants et d’huile dans les réservoirs, séparateurs d’huile, flash tank, etc.
  • Page 8 Instructions de service Contrôleurs de niveau LW4 and LW5 pour contrôle des niveaux haut et bas T e s t d ' é t a n c h é i t é : R e c o m m a n d a t i o n s d e s é c u r i t é : 7.
  • Page 9 Il est recommandé de déconnecter le relais pendant les périodes d’arrêt par d’autres moyens afin d’éviter de mauvaises alarmes dues à la migration liquide dans ou hors du réservoir Note2: LW4X-… et LW5X-… sont calibrés différemment des LW4-… et LW5-…afin d’être utilisés avec des connexions sur réservoir étroites (1/2”, 12 mm) Emerson Climate Technologies GmbH www.emersonclimate.eu...
  • Page 10 C o m p o n e n t e s d e l S i s t e m a : F i g . 1 LW4/5 incorpora un sensor Hall para medir el nivel de líquido del refrigerante y Leyenda Descripción Leyenda Descripción...
  • Page 11 Instrucciones de funcionamiento Sistemas de supervisión de nivel de líquido LW4/LW5, controles de nivel bajo o alto T e s t d e f u g a : I n s t r u c c i o n e s d e s e g u r i d a d : 7.
  • Page 12 Nota 2: LW4X-… y LW5X-… están calibrados diferentes de LW4-… y LW5-…y destinados a ser utilizados con conexión muy estrecha (1/2”, 12 mm) al recipiente.
  • Page 13 I n f o r m a z i o n i g e n e r a l i : C o m p o n e n t i d e l s i s t e m a : Fig. 1 LW4/5 incorporano un sensore di Hall per misurare il livello di refrigerante Legenda Descrizione Legenda Descrizione liquido e olio nei ricevitori, separatori olio, flash tank e riserve di olio.
  • Page 14 Instrucciones de funcionamiento Sistemi di monitoraggio LW4/LW5 per il controllo del livello alto o basso del liquido Attenzione: I s t r u z i o n i d i s i c u r e z z a : •...
  • Page 15 OFF per evitare falsi segnali di allarme a causa della migrazione di liquido dal o nel recipiente. Nota2: LW4X-… e LW5X-… sono calibrati differentemente rispetto a LW4-… e LW5-…e progettati per utilizzo con connessioni del recipiente molto piccole (1/2”, 12 mm).
  • Page 16 О б щ а я и н ф о р м а ц и я : К о м п о н е н т ы : P и с . LW4/5 использует датчик Холла для измерения уровня жидкого хладагента № на № на...
  • Page 17 усилием 50 Нм. Следуйте пунктам 4-8. с максимальным рабочим давлением системы для других применений. Удалите картон, который (9) защищает винты и стекло во время транспортировки. Emerson Climate Technologies GmbH www.emersonclimate.eu Am Borsigturm 31 I 13507 Berlin I Germany Date: 25.07.2019...
  • Page 18 Внимание1: Пожалуйста, обратите внимание на колебание уровня жидкости в процессе работы системы и выключение (переход жидкости из или в сосуд). Рекомендуется обесточить реле во время стоянки во избежание ложного сигнала вследствие миграции жидкости из или в сосуд. Внимание2: LW4X-… и LW5X-… имеют отличную калибровку от LW4-… и LW5-…и предназначены для использования с подключением к сосуду 1/2”, 12 мм.