Introduction
1.2 Safety Notes
Quick Start Guide Safety Information for Hazardous Areas
Note
Ratings under this heading apply to specific model families
Check Your Model Number:
FUS1010 7ME3531, FUH1010, 7ME3601, FUG1010 7ME3611 only;
FM-CSA installation
Read, understand and follow all safety instruction on the electronic media provided. This
equipment is rated for use in hazardous (classified) locations as stated below and must be
installed according to the 1010-341 installation drawing provided on the media. Failure to install
the equipment in the prescribed manner will result in unsafe operation. Follow all local
jurisdictional safety codes when operating this equipment. When properly installed the
equipment meets the following FM–CSA ratings:
Flow Meter
● Explosionproof for Class I, Division1, Groups B, C, D;
● Dust-ignitionproof for Class II, Division 1, Groups E, F and G
● Intrinsically safe connections for Class I and II, Division 1, Groups A, B, C, D, E, F and G;
● Nonincendive for Class I, Division 2, Groups A, B, C and D;
● Suitable for Class II Division 2 Groups E, F and G outdoor (Type 4X)
Transducers
● Intrinsically safe connections Class I and II, Division 1, Groups A, B, C, D, E, F and G;
● Nonincendive for Class I, Division 2, Groups A, B, C and D;
● Suitable for Class II Division 2 Groups F and G outdoor (Type 4X)
● Temperature code T5 at an ambient of 40°C
ATEX installation
Read, understand and follow all safety instruction on the electronic media provided. This
equipment is rated for use in explosive atmospheres as stated below and must be installed
according to the 1010-422 installation drawing provided on the media. Failure to install the
equipment in the prescribed manner will result in unsafe operation. Follow all regional safety
laws when operating this equipment. When properly installed the equipment meets the
following ATEX ratings as stated in EC-Type Examination Certificate KEMA03ATEX2133
10
FUS1010 IP65 NEMA 4X Quick Start
Operating Instructions, 12/2008, CQO:QSG002 Revision B