Télécharger Imprimer la page

SOMFY 1870453 Notice D'installation page 8

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 10
EN
A
MOUNTING
[1] Choose the optimal location: flat and large surface
[2] Mount the LON 4 DC Motor Controller WM
[3] Use cable tie!
[4] Keep to minimum distance
B
CABLING
[1] Tool for all terminals
[2] Wiring diagram
[3] Check the correct running direction of the end product
UP: the end product goes up ( C + )
STOP: the end product stops ( C + + )
DOWN: the end product goes down ( C + )
m To close window press UP, to open window press DOWN.
[4] Possible switches
1.
Smoove Origin IB, Ref. 1811272
2.
Double push button
CHARACTERISTICS
Supply voltage
Power Supply
Stand-by current / Stand-by power (IEC 62301)
LON transceiver
Max. motor current consumption
Supply voltage of group control input
Supply voltage of local push buttons
Terminals
Relay micro-gap
Terminal LON
Running time per output
Operating temperature
Relative humidity
Material of housing
Housing dimensions (w x h x d)
Weight
Degree of protection
Protection class
Pollution degree
Conformity
CABLE
Connection to ... Cable
Motors
Min.: 2 x 0.6 mm/22 AWG / Max.: 2 x 2.5 mm
Switch
Min.: 3 x 0.6 mm/22 AWG / Max.: 3 x 2.5 mm
Group control
Min.: 3 x 0.6 mm/22 AWG / Max.: 3 x 1.5 mm
LON bus
2 x 0.8 mm/20 AWG
24 V DC
Min.: 2 x 1.5 mm
We care about our environment. Do not dispose of the appliance with usual household waste. Give it to an approved collection point for recycling.
m Control of non Somfy motors only on request and after approval by Somfy
24 V DC (min. 21.5 V - max. 28 V DC)
Regulated and short circuit proof power supply, certified and suitable for the connected motors
37 mA@24 V DC / 890 mW@24 V DC
FTT
4 x 2.5 A@24 V DC
SELV, 16 V DC
SELV, 16 V DC
Spring connectors
μ
LON bus terminal (green)
Max. 5 minutes
0 ° C ... 45 ° C
Max. 85 %
PC-ABS
180 x 255 x 61 mm
710 g
IP 20
2
www.somfy.com/ce
/13 AWG –
2
/13 AWG Recommended
2
/15 AWG Recommended
2
/15 AWG / Max.: 2 x 2.5 mm
/13 AWG –
2
2
C
COMMISSIONING AND OPERATING
[1] Attach the Motor Controller address label in accordance with the motor
output in a plan or a list.
[2] Reset/Prog button
Factory reset of the LON Motor Controller.
Twisted pair
Required, following LON topology guidelines
Max. length
Stripping length
6 mm/0.24"
100 m/330 ft
6 mm/0.24"
100 m/330 ft
6 mm/0.24"
6 mm/0.24"
10 m/33 ft
6 mm/0.24"
animeo LON 4 DC Motor Controller WM. Ref. 5138036A -
8/20

Publicité

loading