6.3.2 Emergency Stop Activated
EN
If this message appears in the display, one or more emergency stops have been activated and the machine has
been switched off.
Find out why the emergency stop has been activated and correct the problem. When all hazards have been elim-
inated that activated the emergency stop, the emergency stop can be reset.
• Press 'OK' to reset the Emergency Stop Button.
For more information, see the PLC Setting Manual and the Installation and Service Manual.
Emergency Stop
Activated
Th 11:23
Reset
E-Stop And Press
OK==>
6.3.3 Low Pressure or Duct Isolation Released
The Compressed Air Switch (CAS) indicates that the compressed air pressure is too low.
Check that the compressed air supply is attached to the unit. Reconnect the compressed air supply if necessary.
If the compressed air supply is connected correctly but the compressed air supply is too low, see the PLC Set-
tings Manual and the Installation and Service Manual.
• Press 'OK' to reset the alarm.
Low Pressure
CAS<3Bar Or
Duct Isolation
Valve Released
Th 11:23
Reset OK ==>
6.3.4 Exhaust Air Temp High
The temperature of the air exiting the pump has exceeded the maximum allowable limit of 135°C (275°F).
• When the 'Current Value' has become lower than 90°C (194°F), press 'OK' to reset the alarm and check for the
cooling air valve or PT100 sensor values.
Max Temp Exhaust
Air Exceeded
Unit is Stopped
Limit
135 °C
Current
Reset OK Æ
26
ESC
ESC
130 °C
ESC
FlexPAK
OK
OK
OK