Use cable protection for the 230 V cable when leading through plaster.
Insert the 230 V cable/cable for additional connections protruding from the wall through the
respective openings of the smoke switch housing.
Guide 230 V power cable through smoke switch housing and shorten to approx. 80 mm (1.).
X
Route 24 V cable of electrical hold-open device in the upper guidance of the smoke switch
X
housing (2.).
Align smoke switch housing and screw it firmly to moving-leaf guide rail and frame (3.).
X
Fuse the on-site mains connection with a B10 fuse.
X
Place (2.) the mains cable provided on site on the terminal and connect (3.).
X
Place (4.) the 230 V supply line of the power pack starting from the terminal and stow away extra length in the
X
power pack.
Close and screw on cover of smoke switch housing (5.).
X
Place 24 V output cable into the inside of the smoke switch housing (6.). Protect both 24V cables with foam
X
lining against falling off (7.).
Mounting and securing