Télécharger Imprimer la page

Omron VARISPEED V7 Guide De Démarrage Rapide page 39

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 74
Step 3 – Initializing parameters
To initialize the drive parameters to factory defaults, set parameter n001 = 12.
This will set the V7 to accept START/STOP commands in what in termed "2-wire control", i.e. 1 wire
for a motor FORWARD/STOP command, and 1 wire for a motor REVERSE/STOP command.
Key
Indicator
sequence
In approx.
1 s.
Step 4 – Set the motor rated current
This parameter is used for the electronic thermal function for motor overload detection (OL1). By correctly setting this, the
V7 will protect an overloaded motor from burning out.
Read the rated current (in amps) on the motor nameplate, and enter this into parameter n036. The example to the below
shows entering a value of 1.8Amps.
Key
Indicator
sequence
In approx.
1 s.
Step 5 – Set the motor rated frequency
This is the maximum frequency the motor can run and allows the V7 to properly control the motor.
Read the rated frequency (in Hz) on the motor nameplate, and enter this into parameters n011.
EN-10
Display
Explanation
example
Power On
Press the Mode Key repeatedly until the PRGM indicator is lit.
Press the Enter Key. The data of n001 will be displayed.
Use the Increment or Decrement Key to set n001 to 12. The
display will be lit.
Press the Enter Key so that the set value will be entered and
the data display will be lit.
The parameter number will be displayed.
Display
Explanation
example
Displays the parameter number.
Use the Increment or Decrement Key until n036 is displayed.
Press the Enter Key. The data of n036 will be displayed.
Use the Increment or Decrement Key to set the rated motor
current. The display will flash.
Press the Enter Key so that the set value will be entered and
the data display will be lit.
The parameter number will be displayed.

Publicité

loading

Ce manuel est également adapté pour:

Cimr-v7az