4.There is a failure code on the regulator.
E1: temperatureprobe room faulty (15)
E2: temperatureprobe vaporizer faulty (on the tinnest coppertube) (7)
HA1: maximum temperature alarm
(defrosting doesn't stop or temperaturprobe vaporizer fails)
Ad2: defrost end temperature is not reached in the expected time
OPd: opend door alarm
5.The cooling battery is fully covered with ice.
Stop the cooling unit untill all the ice in the vaporizer has disappeared.
Probably there is a problem with the temperatureprobe of the vaporizer
or
there comes many freshair in in the coolbox.
6. Water is leaking out of the condensation bucket.
Clean – unblock the condensation outlet-pipe (14)
Fill up an eventual leakage past the condensation box with silicone.
7. The compressor works further even if the wished temperature has been
reached.
Check if the indication lamp from the compressor (5) burns on the electronic
control, if not, the contact from the compressor stays closed while it has to be
open. Replace the electronic control.
8. The temperature on the display is not the real temperature in the box.
Place a new temperaturesensor
9.The fans inside the box don't turn.
Are they blockaded or rust ?
Or they commanded by controller ? (does fan shine on the controller ?)
if no, or the evaporator temperature sensor is faulty
or there is not enough refrigerant in the system