Confi Guration - Camille Bauer SINEAX TV 808-12 Mode D'emploi

Masquer les pouces Voir aussi pour SINEAX TV 808-12:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

10.3 Connecting the power supply leads
Connect the power supply leads to terminals 5 ( ) and
10 ( ).
A two-pole switch must be included in the supply connection
where facility for switching SINEAX TV 808 off is desired.
Note:
An external supply fuse must be provided for DC
supply voltages > 125 V.
11. Confi guration
The SINEAX TV 808 unit has to be opened before it can be
confi gured (see Section "8. Withdrawing and inserting the
device").
11.1 Standard input ranges
Soldered jumpers are provided for the coarse setting of the
input ranges and the fi ne adjustment is accomplished using
the potentiometers "Zero" and "Span".
100 must be added to the designations of the soldered jumpers
in the table for channel 1 and 200 for channel 2.
Example: Input range for input 1 and input 2 = 0...20 mA.
Jumpers 1, 5, 6 and 11 must be inserted for this range.
– The corresponding jumpers for channel 1 are B101, B105,
B106 and B111.
– The corresponding jumpers for channel 2 are B201, B205,
B206 and B211).
Current [mA]
0
... 0.1
1, 3 7, 10, 11
0
... 0.2
1, 3 8, 11
0
... 0.5
1, 4 9, 10, 11
0
... 1
1, 4 7, 10, 11
0
... 2
1, 4 8, 11
0
... 5
1, 5 6, 7, 8, 10, 11
0
... 10
1, 5 10, 11
0
... 20
1, 5 6, 11
0.2 ... 1
1, 4 8, 10, 11
1
... 5
1, 4 6, 9
2
... 10
1, 5 6, 7, 10, 11
4
... 20
1, 5 6, 7, 8, 11
0.1 ... 0 ... + 0.1
1, 3 8, 11
0.2 ... 0 ... + 0.2
1, 3 7, 9
0.5 ... 0 ... + 0.5
1, 4 7, 10, 11
1
... 0 ... + 1
1, 4 8, 11
2
... 0 ... + 2
1, 4 6, 9
5
... 0 ... + 5
1, 5 10, 11
– 10
... 0 ... + 10
1, 5 6, 11
– 20
... 0 ... + 20
1, 5 6, 7
Soldered jumpers
12, 15
12, 15
12, 15
12, 15
13, 14, 16
13, 14, 16
13, 14, 16
13, 14, 16
13, 14, 16
13, 14, 16
13, 14, 16
13, 14, 16
Voltage [V]
0
... 0.06
0
... 0.1
0
... 0.2
0
... 0.5
0
... 1
0
... 2
0
... 5
0
... 10
0
... 20
0
... 40
0.2 ... 1
1
... 5
2
... 10
4
... 20
0.1 ... 0 ... + 0.1
0.2 ... 0 ... + 0.2
0.5 ... 0 ... + 0.5
1
... 0 ... + 1
2
... 0 ... + 2
5
... 0 ... + 5
– 10
... 0 ... + 10
– 20
... 0 ... + 20
11.2 Standard output ranges
Soldered jumpers are provided for the coarse setting of the
output ranges and the fi ne adjustment is accomplished using
the potentiometers "Zero" and "Span".
Soldered jumpers
Current
Channel
Channel
[mA]
1
2
0 ... 20
B120
B220
4 ... 20
B121
B221
± 20
–––
–––
11.3 Specifi c user output ranges
Units that have been confi gured for a specifi c user output
range cannot be subsequently reconfi gured.
Span 2
Zero 2
Span 1
Zero 1
Fig. 8. Position of the soldered jumpers B..., potentiometer "Zero"
and "Span".
Soldered jumpers
6, 9, 10, 11
7, 8, 10, 11
6, 8, 9, 11
6, 7, 8, 9, 10
2
6, 7, 8, 10, 11
2
7, 8, 9, 11
2
8, 10
1
10, 11
1
6, 11
1
8
2
9, 10, 11
12, 15
2
6, 8, 9, 10
12, 15
1
6, 7, 10, 11
12, 15
1
6, 7, 8, 11
12, 15
6, 8, 9, 11
13, 14, 16
6, 7, 9, 10
13, 14, 16
2
7, 8, 10, 11
13, 14, 16
2
7, 8, 9, 11
13, 14, 16
2
6, 8, 9, 10
13, 14, 16
1
10, 11
13, 14, 16
1
6, 11
13, 14, 16
1
8
13, 14, 16
Soldered jumpers
Voltage
Channel
Channel
[V]
1
B120
B220
0 ... 20
B122
B222
B123
B223
B121
B221
2 ... 10
B122
B222
B123
B223
B122
B222
± 10
B123
B223
2
19

Publicité

Table des Matières
loading