Adjustment ETM
Attention:
Do not change the distance to the detecting object or the filling level during the adjustment
The EasyTeach-Adjustment provides the possibility for full or empty adjustment. We recommend, always to
do the FULL ADJUSTMENT. Ensure that the active area of the sensor is in contact with the product to be
detected or the product is placed in the active area of the sensor. The full adjustment does not require an
empty adjustment beforehand. When the adjustment with the product to be detected is not possible, an empty
adjustment can be made, e. g. the product to be detected is not known at the time of the sensor adjustment,
but an overfilling must be excluded. When the level is filled for the first time, we recommend making a full
adjustment so that the sensor is optimally adjusted on the material to be detected.
Empty adjustment - Active surface free
• The active surface of the sensor is free.
• Hold the teach magnet on the EasyTeach spot until the LED flashes
green (see EasyTeach-Chart).
• Remove teach magnet.
• During the initialization process the LED is flashing green with higher
frequency.
The empty adjustment is finished when the LED is static green. With this
adjustment the sensor has the largest sensing distance that is possible
at the current mounting position. The switching hysteresis is calculated
automatically.
Full adjustment - Active surface covered
• The active surface of the sensor must be covered completely with the
product to be detected or the product must be in the desired position.
• Hold the teach magnet on the EasyTeach spot until the LED flashes
yellow (see EasyTeach-Chart).
• Remove teach magnet.
• During the initialization process the LED flashes yellow with higher
frequency.
The full adjustment is finished when the LED is static yellow. The sensor
is now optimally adjusted for the detection of the product currently being
used and the current mounting conditions. The switching hysteresis is
calculated automatically.
Test function
The test function can be used to check that the sensor is connected correctly.
• Hold the teach magnet on the EasyTeach spot until both LED's flash at the same time (see Ea-
syTeach-Chart). The output A1 pulses accordingly.
The test function is activated until you remove the teach magnet. The adjusted values stay unchanged.