Chauvin Arnoux MiniFLEX MA200 Notice De Fonctionnement page 21

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 1
Press the yellow opening device to open the flexible coil.
Open it, then place it round the conductor through which the current to be measured
flows (only one conductor in the sensor).
Close the coil. In order to optimize measurement quality, it is best to centre the
conductor in the coil and to make the shape of the coil as nearly circular as
possible.
Set the switch on the housing to the range that provides the best sensitivity.
Read the measurement on the oscilloscope, applying the reading coefficient indi-
cated on the label of the housing corresponding to the setting of the switch.
30 A~ rating
300 A~ rating
3000 A~ rating
2.2.2. DISCONNECTION
Remove the flexible coil from the conductor, then disconnect the housing of the
multimeter or oscilloscope.
100 mV~/A~
10 mV~/A~
1 mV~/A~
21

Publicité

Table des Matières
loading

Table des Matières