Télécharger Imprimer la page

Technical Specifications - Johnson Controls VP140 Serie Instructions D'installation

Masquer les pouces Voir aussi pour VP140 Serie:

Publicité

Technical specifications

The following section describes technical specifications valve and the electro-mechanical actuator.
Flow rate max. (100% water)
Service
Accuracy up to 15 PSID = 100 kPa
Minimum ΔP for start-up
Maximum ΔP
Maximum working pressure
Close off pressure
Temperature
Connection
Leakage
Compliance
Flow rate max. (100% water)
Service
Accuracy up to 15 PSID = 100 kPa
Minimum ΔP for start-up
Maximum ΔP
Maximum working pressure
Close off pressure
Temperature
Connection
Leakage
Compliance
Table 1: VP140 Axx 1/2" (DN15)
VP140AAA
0.66 GPM, 150 l/h
Water or water-glycol mixture (up to 50% glycol), quality to VDI 2035
2.9 psi
20 kPa
Johnson Controls, Inc., declares that this product is in compliance with the essential requirements and other relevant provisions of
the PED (Pressure Equipment Directive).Service
Table 2: VP140 Bxx 3/4" (DN20)
VP140BAJ
4.4 GPM,1,000 l/h
Water or water-glycol mixture (up to 50% glycol), quality to VDI 2035
4.4 psi
30 kPa
Johnson Controls, Inc., declares that this product is in compliance with the essential requirements and other relevant provisions of
the PED (Pressure Equipment Directive).
VP140AAE
2.6 GPM, 600 l/h
± 5%
3.6 psi
25 kPa
87 psi
600 kPa
362 psi
2495 kPa
100 psi
689 kPa
14 to 248 °F
-10 to 120 °C
½" FNPT
ANSI Class IV IEC 60534-4
VP140BAN
6.6 GPM, 1,500 l/h
± 5%
5.1 psi
35 kPa
87 psi
600 kPa
362 psi
2495 kPa
100 psi
689 kPa
14 to 248 °F
-10 to 120 °C
¾" FNPT
ANSI Class IV IEC 60534-4
17
VP14AAG
3.4 GPM, 780 l/h
5.1 psi
35 kPa
VP14BAU
9.7 GPM, 2,200 l/h
3.6 psi
25 kPa
¾" FNPT Union
P/N 14-88360-03389, Rev.A

Publicité

loading

Ce manuel est également adapté pour:

Vp140aaaVp140aaeVp140aagVp140bajVp140ban